Associated batteries: recombination-type lead, capacity depending on charger ratings: 1.2Ah; 2.1Ah; 7Ah;
12Ah; 17Ah; 24Ah; 40Ah / floating recharge at C/10.
Environmental specifications: operating temperature: - 5°C to 50°C / storage temperature: - 25 to + 85°C
/ operating relative humidity: 20 to 95%.
Electrical input specifications: single-phase voltage: 230V (195.5V-264.5V) / frequency: 50-60Hz (from
45 to 65Hz) / neutral systems: TT, TN, IT / a D curve circuit breaker with easy access to be provided upstream
/ primary current @230V: 0.25A (12V 2A - 24V 1A); 0.75A (12V 5A - 24V 2.5A); 1A (12V 10A - 24V 5A).
Electrical output specifications: "floating" load output in relation to the ground / float voltage: 13.6V (12V
2A - 12V 5A - 12V 10A); 27.2V (24V 1A - 24V 2.5A - 24V 5A) / current limitation: 1A (24V 1A); 2A (12V 2A);
2.5A (24V 2.5A); 5A (12V 5A – 24V 5A); 10A (12V 10A).
Alarm reports: 2 dry contacts (open when faulty) 1A@24Vdc, 0.5A@120Vac: mains fault or rectifier fault /
battery low voltage fault - Indicated by a LED on the front panel.
Protection: fuses on electronic board - see table « mother board fuses ».
Mains:
Caution! This equipment is designed to be connected to the 230 Vac public distribution
network, an easily accessible isolating switch must therefore be installed outside of the
cabinet.
Use a 2A bipolar D curve circuit breaker to connect the power supply to the mains circuit.
Connections: cable section, mains, load, battery alarm reports: 0.3 to 2.5 mm² (12V 2A - 12V 5A - 24V
1A - 24V 2.5A); 0.3 to 6 mm² (12V 10A – 24V 5A) / length to be stripped: 7mm / The bare parts of the
cables must be crimped before being wired to the terminals of the product.
Commissioning and operation instructions can be downloaded from www.slat.com
No equipment may be returned without prior issuance of an RMA number.
For additional technical assistance, or to request and RMA number,
contact the SLAT hotline on +33 (0) 4 78 66 63 70
Product warranty: 3 years, cf. our general sales terms