Télécharger Imprimer la page

D+H ZA 35-K-BSY Manuel D'utilisation page 6

Publicité

Les langues disponibles

Les langues disponibles

WARNING
Read all safety warnings, instructions, illustrations
and specifications provided with this product.
Failure to follow all instructions listed below may
result in electric shock, fire and/or serious injury.
Save all warnings and instructions for future
reference.
Safety notes
Operating voltage 230 V AC!
Risk of injury from electric shock!
Do not reverse L+N! Connect PE!
The BSY+ bus also operates with 230 V!
- Connection must be carried out by a certified
electrical technician
- Danger of crushing hands and fingers!
- Keep people away from the operating area of
the drive
- Keep children away from the control
- Observe pressure load diagram of the gear rack!
- Use only in dry rooms
- Suitable for indoor mounting only. Use rain
detector in the event that there is a risk of rain
- Use option "-W" if mounted outdoors!
- Use unmodified original D+H parts only
- Observe the bracket-set mounting instructions
Observe enclosed red safety note!
Mounting information
- Swivel radius of the drive must go free over entire
range of stroke. Otherwise, the toothed rack and
the suspension can be damaged.
- Drives with a stroke of ≥800 mm must not be moun-
ted „hung up at the bottom" (e.g. bracket UK).
- The drive set will be full configured by factory.
The drives must be reconfigured in case of
alterations (e.g. removing of drives from existing
set or integrating a new drive) with SCS*.
- Use only drives with the same force.
- Ensure evenly load distribution on all the drives.
- Eyebolt has to be adjusted so, that the drive is
disconnected with closed flap through it's inside
stop position damping. Brackets can be damaged
by to rigid adjustment!
* only with BI-BT2 (electronically isolated due to Bluetooth)
6/20
ZA-K-BSY+
Intended use
- Rack and pinion drive for electric opening and
closing of windows and flaps in the facade and
roof area
- Operating voltage 230 V AC
- Up to 4 drives possible
- Useable for smoke extraction, D+H Euro-SHEV in
accordance with DIN EN 12101-2 as well as daily
ventilation
- Suitable for indoor mounting only
Features
- Microprocessor-controlled synchronous
electronics BSY+ for safe and precise
synchronous running of up to 4 drives
- Individually programmable via software SCS*
- SHEV-high speed function (fast-running feature in
OPEN-direction)
- Closing edge protection for the main closing edge
- Especially quiet motor running in ventilation mode
- Optinal with "-AS2" = protection class 2 and
"-AS3" as well as "-LS" = protection class 3
Scope of supply
Drive unit with 2.5 m silicone cable. Depending on
the type of window, different bracket sets are
available separately.
Pressure load diagram
Maximum pressure load of the toothed rack is not
automatically identical with maximum pressure force
of the drive!
Loads from over 1000 N to 1500 N are only briefly
permissible (e.g. to throwing off snow or with wind
loads). These may arise up to a stroke of 800 mm.
1400
1200
1000
800
600
400
200
0
English
durable
temporary
Stroke (mm)
99.823.99 2.1/09/23

Publicité

loading