Installation
Installation
NOTICE! Avoid cleaners containing organic
solvents, alcohols, and hydrocarbons.
Rinse with water after cleaning.
Supplies Required
• (3) ³⁄₈" wall fasteners and bolts
• Pipe sealant
• Piping to ½" IPS water supply inlet on unit
• Piping to 1¼" IPS drain outlet
• Sign-mounting hardware
Step 1: Install Inlet Drain Fitting
The top of the eyewash heads should be
33"–45" (838mm–1143mm) from the floor.
1. Position the inlet drain fitting over the 1¼" drain
outlet pipe from wall.
2. Using the inlet drain fitting as a template, mark
the bolt hole locations on the wall OR install three
suitable fasteners (supplied by installer) for ³⁄₈" bolts
in the wall at the marked hole locations
(see Figure 1).
3. Bolt the inlet drain fitting to the wall or wall
fasteners using ³⁄₈" bolts (supplied by installer).
Step 2: Assemble Eye/Face Wash
1. Assemble eyewash components as shown in Figure 2.
• Apply pipe sealant (supplied by installer) to all male-threaded pipe joints.
• Use the rubber grip pad provided or a strap wrench around pipes when tightening to prevent marring the
Bradtect
protective, safety yellow coating. Place the grip pad on the pipe, then put the wrench over the grip
®
pad and turn the pipe with the wrench.
Step 3: Connect Water Supply
1. Connect the water supply piping (supplied by installer) to the ½" IPS inlet on the eye/face wash.
2. Connect the tailpiece to the 1¼" IPS drain outlet on the eyewash.
3. Mount the safety sign to the wall using sign-mounting hardware (supplied by installer).
4. Open the water supply lines. Test for leaks and adequate water flow.
Bradley • 215-1939 Rev. A: ECO 22-05-062B
Bradley
Figure 1
Wall
13¼"
(337mm)
Ø 10" (254mm)
15½" (394mm)
8¹⁄₈"
(206mm)
2¼"
(57mm)
Ø ³⁄₈"
(9mm)
5¼"
(133mm)
12/19/2022
S19-222
4½"
(114mm)
8¼"
(210mm)
4"
(102mm)
36" (914mm)
Suggested
Height to
Floor
29½"
(749mm)
Suggested
Height to
Floor
3