CONVERTING YOUR FIRE PIT TO NATURAL GAS
This Conversion should only be performed by a Qualified Service Technician or Licensed Plumbe
1.
MAKE SURE THAT THE GAS SUPPLY TO THE FIRE PIT (AND ANY NEARBY ELECTRICAL
SOURCES/APPLIANCES) ARE SHUT OFF.
Carefully detach the flex line connector hose attached to the orifice holder (Figure # 1) and unscrew the orifice holder
2.
from the burner pipe (Figures #1 and # 2).
Remove the orifice from the holder (Figure # 2 ) and replace it with the proper sized one for your gas requirement.
3.
Propane requires the smaller orifice.
If you are converting from propane (LP) gas to natural gas, install the air shutter sleeve so that the air intake holes are
4.
closed (Figure #2). For Propane gas, remove the air shutter so that the air intake holes are open (Figure #1). After the
unit is assembled for use, you are required to do a "leak check" by using a liquid soapy solution on all connections
before placing the unit in operation.
IT IS NECESSARY TO ATTACH THE LABEL OR RATING PLATE INCLUDED WITH THE CONVERSION KIT TO
5.
CLEARLY INDICATE THE FIELD CONVERSION.
Burner
Orifice
Air Intake hole open for LP Gas
Burner
Orifice
When converting to natural gas, the air shutter
sleeve MUST be installed over the burner pipe.
MANUFACTURER'S USE ONLY
Model #
Orifice Installed
Orifice Included
Air Shutter Sleeve
Gas Type
FIGURE 1
Orifice Holder
FIGURE 2
Orifice Holder
QUALITY CHECK
COM0580
#40 - Liquid Propane
NG #31 COM0580CK
Included
Liquid Propane
Flex Line
Connector Hose
Follow steps 1 – 5 shown above.
THE CONVERSION MUST BE CARRIED OUT
BY A QUALIFIED SERVICE AGENCY, IN
ACCORDANCE WITH THE REQUIREMENTS OF
THE MANUFACTURER, PROVINCIAL OR
TERRITORIAL AUTHORITIES HAVING
JURISDICTION AND IN ACCORDANCE WITH
THE REQUIREMENTS OF THE CAN/CGA-
B149.1 OR CAN/CGA-B149.2
INSTALLATION CODES.
Flex Line
After conversion follow Operating Instructions
Connector Hose
found on Page 12.
After The Unit Is Converted, it Must Be
Tested to Verify the Inlet and Manifold
pressures are as specified on Page 3.
Additionally, a qualified service agency must
verify that the input rate of the converted
appliance match the rating listed below.
Date
Serial Number
Work Order #
BTU Rating
Inspector
Leak Test
Burn Test
Page 14
Casual Fireside Fire Pits Are
Suitable For Installation from
0 - 4,500 ft. Without Modification.
LP 60,000 / NG 62,500