DC Inverter U-match Series Cassette Type Unit
Model
3
2
NOTES:
Fuse is located on the main board.
Install a circuit breaker near the outdoor units with at least 3mm
contact gap. The units must be able to be plugged or unplugged.
Circuit breaker and power cord specifications listed in the above table
are determined based on the maximum power input of the units.
Supply cords of parts of appliances for outdoor use shall not be lighter
than polychloroprene sheathed flexible cord (code designation 60245
IEC 57).
Specifications of circuit breaker are based on a working condition
where the working temperature is 40°C. If working condition changes,
please adjust the specifications according to national standards.
Adopt 1.0mm² power cords between indoor and outdoor units. The
maximum length of 35-85 units is 30m and the maximum length of
100-160 units is 75m. Please select a proper length according to local
conditions. To be in compliance EN 55014, it is necessary to use 8
meters long wire.
Adopt 2pc of 0.75mm² power cords to be the communication cords
between wired controller and indoor unit. The maximum length is 30m.
Please select a proper length according to local conditions.
Communication cords must not be twisted together. To be in
compliance EN 55014, it is necessary to use 8 meters long wire.
Power supply
V/Ph/Hz
380-415V ~50/60Hz
38
Circuit
Min. sectional area
breaker
of power cord
capacity
A
16
16
16
16
mm²
1.5
1.5
1.5
1.5