Montageanleitung Rohbau
DE
für PushPull Lüftungssysteme
Shell mounting instructions
UK
for PushPull ventilation systems
Notice de montage Gros œuvre
FR
pour systèmes de ventilation PushPull
www.ait-deutschland.eu
LD 45 RH 500
LD 45 RH 800
LD 45 ABK
LD 45 AB-VA
LD 45 AB-AL
LD 45 LBE
LD 45 LEV
LD 30 AK
LD 30 AW
LD 30 AE
!

Publicité

loading

Sommaire des Matières pour ait-deutschland LD 45 RH 500

  • Page 1 PushPull Lüftungssysteme Shell mounting instructions for PushPull ventilation systems Notice de montage Gros œuvre pour systèmes de ventilation PushPull LD 45 RH 500 LD 45 RH 800 LD 45 ABK LD 45 AB-VA LD 45 AB-AL LD 45 LBE...
  • Page 4 Für Lieferumfang der Außenabdeckung Für weiterführende Informationen zur Endmon- siehe Beiblatt Außenabdeckung. tage siehe: Rohbauhülse kurz LD 45 RH 500 (15922001) ● Lüftungsgerät mit beigefügter Montage- Rohbauhülse lang LD 45 RH 800 (15922101) anleitung Endmontage-Set Wandhülse, Putzschutzdeckel und Keile. Für ●...
  • Page 5 2 Qualifikation Fachinstallateur | DE ● LD 30 ARW (Ausgleichsrahmen weiß) mit Zur Verfügung stehen LD 45-Geräte in den dem Befestigungsblech LD 30 ARW BB Ausführungen Objekt „O“, Komfort „K“ und die wird für die Montage von LD 30 AW und LD funkgesteuerten Varianten „RC“. 45 ABK/LD 45 AB-AL verwendet.
  • Page 6 DE | 4 Sicherheitshinweise und Warnungen Explosionsgefahr: Explosionsfähige 4 Sicherheitshinweise und Gase und Stäube können entzündet wer- Warnungen den und zu schweren Explosionen oder Brand führen.  Lüftungsgerät auf keinen Fall in Warnhinweise: Symbole, Bedeutung explosionsfähiger Atmosphäre einsetzen. GEFAHR: Zeigt eine mögliche Gefahren- Explosionsgefahr: Explosionsfähige situationen, die zum Tod oder ernsten Verlet- Stoffe in Laborabsaugungen können...
  • Page 7 4 Sicherheitshinweise und Warnungen | DE LD 30-Lüftungsgeräte vorzugsweise Verletzungs- und Gesundheitsgefahr in Ablufträumen einsetzen (Bad, WC bei Einsatz von nicht zugelassenen oder Küche mit Fenster). Zubehörkomponenten. Das Lüftungsgerät  LD 30-Lüftungsgeräte nur nach Abstim- ist mit Original-Zubehörkomponenten (z. B. mung mit dem Eigentümer in Zulufträumen Luftfilter) getestet und zugelassen.
  • Page 8 DE | 5 Anwendungsbeispiele Beispiel 2: Lüftungslösung für eine 3-Zimmer 5 Anwendungsbeispiele Etagenwohnung mit Lüftungsgeräten LD 30 BK Beispiel 1: Einzelraumanwendung mit einem (Bad) und LD 45 (Wohnräume). LD 45-Gerätepaar Das LD 30 BK be- und entlüftet gleichzeitig das Badezimmer im balancierten Betrieb. Ein LD 30 BK-Ventilator belüftet den Raum mit der im Wärmetauscher vorerwärmten Luft.
  • Page 9 ● Für den Filterwechsel ausreichend Arbeits- Außendurchmesser DN 160 freiraum vor dem Gerät sicherstellen. Wandhülse LD 45 RH 500: 500 mm ● Kernlochbohrung zur Gerätemontage und (max. Länge) LD 45 RH 800 800 mm Befestigungspunkte der Außen- und Innen- Wandstärke...
  • Page 10 DE | 8 Montagevorbereitungen 8 Montagevorbereitungen 7.3 Anzahl Lüftungsgeräte Kombinationen Anzahl Lüftungsgeräte 8.1 Montagehinweise Lüftungsgeräte Max. 6 LD 45-Geräte ● LD 45-Geräte sind nur für Zulufträume LD 45 O/K + (3 x 2 Gerätepaare). geeignet. Raumluftsteuerung Ab Sternpunkt 25 m LDS 45 O/K Kabelanschlusslänge ●...
  • Page 11 Befestigungsblech LD 30 ARE BB bzw. 9.1 Montage Wandhülse LD 30 ARW BB mit der Wand verschrauben. Ausgleichsrahmen (Tiefe 55 mm) sind stapel- LD 45 RH 500/RH 800 für LD 45-Geräte bar. ● Elektrische Zuleitung entsprechend der Gerätevariante beachten: LD 45 O/K: Steuerleitung J-Y (ST) Y 2 x 2 x 0,8 mm.
  • Page 12 6. Wandhülse mit mitgelieferten Putzschutz- Vorgeschriebener Wandstärke deckeln beidseitig verschließen. Wandhülsen-Überstand 7. Bei einer DN 162-Kernbohrung die Wand- für LD 45 RH 500/RHL hülse mit Montagekleber in der Kernboh- LD 45 ABK/AE/AW W + 10...15 mm rung fixieren. LD 45 LBE W + 20...25 mm...
  • Page 13 9 Montage der Wandhülse und Außenabdeckung | DE Montage Dichtungsstreifen auf die Wandhülse kleben. Geeignetes Dichtungsmaterial ist ! VORSICHT bauseitig bereitzustellen. Vorsicht beim Umgang mit scharf- kantigen Gehäuseteilen, z. B. bei 9.2 Montage Außenabdeckung Edelstahl-Außenabdeckungen Außenabdeckung erst nach Abschluss  Schutzhandschuhe benutzen. der Außenputzarbeiten montieren.
  • Page 14 DE | 9 Montage der Wandhülse und Außenabdeckung Montage LD 30 AK und LD 30 AE/AW – nach Fertigputz der Außenwand – Position der Außenabdeckung und Wandhülse Bohrschablone verwenden! 1. Putzschutzdeckel entfernen, Bohrschablo- ne über die Wandhülse setzen, ausrichten und Befestigungslöcher markieren. Positi- on TOP beachten.
  • Page 15 9 Montage der Wandhülse und Außenabdeckung | DE LD 30 AE/AW LD 30 AE / LD 30 AW: Frontabdeckung anbringen LD 30 AK ! VORSICHT Vorsicht beim Umgang mit scharf- kantigen Gehäuseteilen, z. B. bei Edelstahl-Außenabdeckungen.  Schutzhandschuhe benutzen. 5. Gehäuse [G] mit 4 Schrauben an der Außenwand festschrauben.
  • Page 16 DE | 10 Montage Laibungselement LD 45 LBE ACHTUNG 10 Montage Laibungselement Einbauposition Innenwand: Wandhülse LD 45 LBE muss nach Anbringung von Putz, Tapete etc. LD 45 LBE nicht für LD 30-Geräte putzbündig mit der Innenwand abschließen. geeignet – LD 45 LBE nur mit LD 45- Einbauposition Fensterlaibung: Die Kon- Geräten einsetzen.
  • Page 17 10 Montage Laibungselement LD 45 LBE | DE 6. Laibungselement befestigen: Montagevorbereitungen LD 45 LBE ● Montageposition bestimmen. Auf eine ebene Wandfläche achten. Abmessungen beach- ten. Eine 7 mm umlaufende Putzkante [P] berücksichtigen. ● Außenwand-Fassadendämmung an das Laibungselement anpassen. ! WARNUNG Verletzungsgefahr, falls sich Laibungs- element oder Wandhülse löst.
  • Page 18 DE | 11 Weitere Vorgehensweise bei der Endmontage 2. Aufnahme [4] in den Laibungskanal drücken 12 Einbaumaße und mit 4x beiliegenden Edelstahl-Spax- schrauben vorsichtig verschrauben (nicht LD 45 ABK zu fest). Darauf achten, dass die Aufnah- me im unteren Bereich komplett abgedich- tet ist.
  • Page 19 12 Einbaumaße | DE LD 45 LBEV (nicht mit LD 30 B kombinierbar) LD 30 BO/BK LD 30 BO/K + LD 45 VS Weitere Abmessungen Komponente Abmessungen (BxHxT) LDS 45 O / LDS 45 K 80 x 80 x 49 mm Raumluftsteuerung LDS 45 RC 80 x 80 x 15 mm...
  • Page 20 Please read the instructions see external cover supplement. carefully. Pay particular attention to the safety instructions. Follow the instructions. Shell sleeve, short LD 45 RH 500 Before commissioning, also read the operating (15922001) instructions for the ventilation unit.
  • Page 21 2 Specialist installer qualification | UK LD 30 are balanced ventilation units, which Fixing plate LD 30 ARE BB / ARW BB are the ideal choice for use in exhaust air (0093.1526 / 0093.1527) rooms (bathroom, WC or kitchen with win- Fixing plate for compensating frame dows) and aerate and ventilate the rooms at LD 30 ARE / LD 30 ARW.
  • Page 22 UK | 4 Safety instructions and warnings Risk of explosion: Explosive substanc- 4 Safety instructions and warnings es in lab extraction units may ignite and cause serious explosions or fire. Aggressive Warnings: Symbol, meaning substances may damage the ventilation unit. ...
  • Page 23 4 Safety instructions and warnings | UK Read and observe the following Risk of injury and health risk when using accessories which have not safety instructions. been approved. The ventilation unit is tested Risk of injury if work is carried out by and approved with original accessories (e.g.
  • Page 24 UK | 5 Application examples Example 2: Ventilation solution for a 3-room 5 Application examples flat with LD 30 BK (bathroom) and LD 45 Example 1: Single-room application with a (living spaces) ventilation units. LD 45 unit pair The LD 30 BK aerates and ventilates the bathroom at the same time with balanced operation.
  • Page 25 External diameter Ø 160 work in front of the unit. Wall sleeve LD 45 RH 500: 500 mm ● Do not drill core drill hole for unit assembly (max. length) LD 45 RH 800: 800 mm and do not drill fixing points on external and...
  • Page 26 UK | 8 Mounting preparations 8 Mounting preparations 7.3 Number of ventilation units Combinations Number of ventilation 8.1 Mounting information units ● LD 45 units are only suited for supply air Ventilation units Max. 6 LD 45 units rooms. LD 45 O/K + (3 x 2 unit pairs).
  • Page 27 9.1 Mounting wall sleeve up to star point max. 4 m. PP 45 RC: NYM 3 x 1.5mm² LD 45 RH 500/RHL for LD 45 units LD 30 BO/K: Control cables: type J-YSTY, 0.8 mm, 4 wires. Max. 25 m from star point, up to star point max.
  • Page 28 7. For a 162 core hole, fix the wall sleeve Ø for LD 45 RH 500/RHL with construction adhesive in the core hole. LD 45 ABK/AE/AW W + 10...15 mm 8. For a 182 core hole, align wall sleeve Ø...
  • Page 29 9 Mounting the wall sleeve and external cover | UK Mounting 9.2 Mounting external cover ! CAUTION Only mount external cover once the external plastering is complete. Exercise caution when handling housing parts with sharp edges, Formation of surface rust: External e.g.
  • Page 30 UK | 9 Mounting the wall sleeve and external cover Mounting LD 30 AK and PP 30 AE/AW – once external wall is fully plastered – Position of external cover and wall sleeve Use drilling template! 1. Remove plaster protective cover, place drilling template over the wall sleeve, align it and mark the fixing holes.
  • Page 31 9 Mounting the wall sleeve and external cover | UK LD 30 AE/AW LD 30 AE / LD 30 AW: Attaching front cover LD 30 AK ! CAUTION Exercise caution when handling housing parts with sharp edges, e.g. stainless steel external covers. ...
  • Page 32 UK | 10 Mounting soffit element LD 45 LBE NOTICE 10 Mounting soffit element LD 45 LBE Installation position, internal wall: Once the plaster has been applied or wallpaper put LD 45 LBE not suited for LD 30 units up etc., the wall sleeve must end flush with – use LD 45 LBE only in combination the internal wall.
  • Page 33 10 Mounting soffit elementLD 45 LBE | UK Mounting preparations LD 45 LBE 6. Secure soffit element: ● Determine installation position. Ensure mounting is on a level wall surface. Note dimensions. Take account of a 7 mm plaster edge [P] all the way round. ● Adjust external wall façade insulation to the soffit element.
  • Page 34 UK | 11 Next steps for final mounting 2. Press holder [4] into soffit duct and care- 12 Installation dimensions fully screw down with 4x stainless steel Spax screws provided (not too tight). En- LD 45 ABK sure that the holder is sealed completely at the bottom. 3.
  • Page 35 12 Installation dimensions | UK LD 45 LBEV (cannot be combined with LD 30) LD 30 BO/BK LD 30 BO/BK + LD 45 VS Other dimensions Component Dimensions (WxHxD) LDS 45 O/LDS 45 K 80 x 80 x 49 mm room air control DS45 RC 80 x 80 x 15 mm...
  • Page 36 8 Préparatifs de montage ......44 Consignes de montage .......44 Mentions légales : 9 Montage de la gaine murale et de la © ait-deutschland GmbH. Traduction de la notice protection externe ........45 allemande d'origine. Sous réserve de fautes d'im- Montage de la gaine murale ....45 pression, d'erreurs et de modifications techniques.
  • Page 37 2 Qualification de l’installateur spécialisé | FR Cadre d’adaptation LD 30 ARE / ARW 3 Utilisation conforme (0093.1501 / 0093.1525) Les appareils de ventilation LD 45/LD 30 à ● Cadre d’adaptation pour le montage sur des récupération de chaleur servent à évacuer / murs minces. insuffler l’air des appartements, bureaux ●...
  • Page 38 FR | 4 Consignes de sécurité et avertissements La commande des appareils de ventilation 4 Consignes de sécurité et s’effectue avec une commande d’air ambiant avertissements adaptée pour le type d’appareil : ● Commande LDS 45 O ou LDS 45 K Avertissements : Symboles, significa- pour PP 45 O/K et PPB 30 O/K.
  • Page 39 4 Consignes de sécurité et avertissements | FR Des vapeurs de graisse et d’huile  Ne jamais utiliser l’appareil de ventilation si en provenance de hottes aspirantes un foyer dépendant de l’air ambiant raccordé risquent d’encrasser l’appareil de ventila- à une installation d’évacuation de gaz à garni- tion et de réduire son efficacité.
  • Page 40 FR | 4 Consignes de sécurité et avertissements Risque de blessure lors des travaux Danger de mort dû à la présence de en hauteur. monoxyde de carbone en cas d’uti-  Utiliser des auxiliaires d’accès vertical lisation avec des foyers dépendants de l’air ambiant.
  • Page 41 5 Exemples d’application | FR Exemple 2 : Solution de ventilation dans 5 Exemples d’application un appartement 3 pièces avec appareils de Exemple 1 : Application dans une seule ventilation PPB 30 K (salle de bains) et PP 45 pièce avec une paire d’appareils PP45 (pièces d’habitation) Le PPB 30 K ventile et aère simultanément la salle de bains en cas de fonctionnement...
  • Page 42 FR | 6 Exigences sur le lieu d’installation 6 Exigences sur le lieu 7 Caractéristiques techniques d’installation 7.1 Caractéristiques techniques PP 45 ● Température ambiante de - 15 °C à + 40 °C. ● Température des fluides max. 40 °C. Diamètre extérieur Ø...
  • Page 43 Diamètre extérieur Ø 160 Combinaisons Nombre d'appareils de ventilation Gaine murale LD 45 RH 500 : 500 mm Appareils de ventilation 6 appareils LD 45 max. (longueur max.) LD 45 RH 800: 800 mm LD 45 O/K + (3 x 2 paires d'appa- Épaisseur murale...
  • Page 44 FR | 8 Préparatifs de montage ● LD 30 : L’unité d’insertion (module d’inser- Appareils de ventilation 3 LD 30 BK ou tion + tube de prolongation) doit corres- LD 30 BK + 2 LD 30 BK + pondre à l’épaisseur du mur pour éviter un Commande d'air am- 2 LD 45 O/K ou biant LDS 45 K ou...
  • Page 45 9 Montage de la gaine murale et de la protection externe | FR ● déséquilibres causés par les longueurs LD 45 RH 500/RHL pour appareils LD 30 différentes des câbles de commande. Respecter les prescriptions d’installation re- latives à la longueur et aux types de câbles.
  • Page 46 ! Données pour le mur intérieur et LD 45 RH 500/RHL extérieur une fois crépi. LD 45 ABK/AE/AW W + 10...15 mm 3. Ébarber la gaine murale des deux côtés.
  • Page 47 9 Montage de la gaine murale et de la protection externe | FR Nous conseillons de nettoyer avec soin les 2. Déposer le cache de protection [F] du protections externes en acier inoxydable non boîtier [G] de la protection externe. peint avant le montage (retirer la poussière 3.
  • Page 48 FR | 9 Montage de la gaine murale et de la protection externe Montage de LD 30 AK et LD 30 AE/AW – une fois le mur extérieur crépi – Position de la protection externeet de la gaine murale Utiliser le gabarit de perçage ! 1.
  • Page 49 9 Montage de la gaine murale et de la protection externe | FR LD 30 AE/AW LD 30 AE / LD 30 AW : monter le cache de protection LD 30 AK ! PRUDENCE Manipuler avec prudence les pièces de boîtier à arêtes coupantes telles que les protections externes en acier inoxydable.
  • Page 50 FR | 10 Montage de l’élément d’embrasure LD 45 LBE ATTENTION 10 Montage de l’élément d’embrasure LD 45 LBE Position de montage – mur intérieur : Après application du crépi, du papier peint, LD 45 LBE ne convient pas pour les etc., la gaine murale doit être en affleurement appareils LD 30 –...
  • Page 51 10 Montage de l’élément d’embrasure LD 45 LBE | FR Préparatifs de montage LD 45 LBE 4. Enfoncer l‘élément d‘embrasure jusqu‘en butée sur la gaine murale/le joint en ca- ● Déterminer la position de montage. Veiller à outchouc. Le canal d‘embrasure doit être ce que la surface du mur soit plane.
  • Page 52 FR | 11 Suite de la marche à suivre lors du montage final 11 Suite de la marche à suivre lors 10.1 Grille extérieure d‘embrasure Chap. 8.2) du montage final  Ne pas monter la grille extérieure Consignes de montage du boîtier encastré avant d‘avoir posé le crépi extérieur. Pour le montage des composants de com- En cas de fuites, le joint mural [4.1] sert mande mentionnés ci-dessous, nous conseil- de protection afin que l‘eau de conden- lons l’emploi des boîtiers encastrés en vente...
  • Page 53 12 Cotes de montage | FR 12 Cotes de montage LD 45 LBE (ne peut pas être combiné avec LD 45 ABK LD 30) LD 45 AB-VA / LD 45 AB-AL Longueur à partir du milieu de  l’avant-trou max. Longueur à...
  • Page 54 FR | 12 Cotes de montage LD 45 LBEV (ne peut pas être combiné avec LD 30) LD 30 BO/K LD 30 BO/K + LD 45 VS...
  • Page 55 12 Cotes de montage | FR Autres dimensions Composant Dimensions (lxhxp) Commande d'air 80 x 80 x 49 mm ambiant LDS 45 O / LDS 45 K Interrupteur radio 80 x 80 x 15 mm DS45 RC Module d'extension 80 x 80 x 49 mm LD 45 EO-ER EnOcean Détecteurs externes 80 x 80 x 49 mm...
  • Page 56 FR | 12 Cotes de montage ait-deutschland GmbH Industriestraße 3 95359 Kasendorf Germany info@ait-deutschland.eu ● ● ● ●...