Télécharger Imprimer la page

Accucold MOMCUBE AFZ2PVBIADAMC Mode D'emploi page 17

Publicité

Les langues disponibles

Les langues disponibles

If setting C8 is set to "0", then after the alarm is canceled, the alarm relay will not close. If C9 is set
to"0", then after the alarm cancel button is pushed, the buzzer does not restart.
If setting other numbers, then after reaching delay time, buzzer sounds one more time. (Under the
condition of alarm not terminating)
Error mode: When air sensor is short-circuited or high temperature over limit (> 66 °C /151 °F ), "1H"
is displayed; when air sensor is open-circuited or low temperature over limit (<- 40 °C / °F ) "1L" is
displayed. Compressor will enter the force running mode, according to C10, C11 set parameters
running in sequence.
When product sensor is short-circuited, open-circuited or over limit (>66 °C /151 °F ), alternate display
2H and air temperature, the product temperature sensor open-circuited or low temperature over limit
(<-40°C/°F), alternate display 2L and air temperature.
Alarm Indicator List
Alarm type
Freezer high temp. alarm
Freezer low temp. alarm
Air temp. sensor short-circuited
Air temp. sensor open-circuited
Product temp. sensor short-
circuited
Product temp. sensor open-
circuited
Product temperature high temp.
Product temperature low temp.
Electric supply off alarm
Door open delay alarm
When the door is open, the light switch can turn the light on and off.
Compressor running
Compressor on
Compressor off
Press C10, C11 to run the
comp.
Press C10, C11 to run the
comp.
Limit alarm
Limit alarm
17
Display flash
H1 delay alarm
L0 delay alarm
1H in time alarm
1L in time alarm
2H in time alarm
2L in time alarm
H2 delay alarm
L2 delay alarm
No display and alarm in
time
Dr flash and delay alarm

Publicité

loading