GENERAL
The SPeX is a single-pole plug and receptacle for use in explosive atmospheres
and conforms to the relevant international and European standards, particularly
the ATEx Directive 2014/34/UE. SPeX can be used in zones 1 and 2 (gas) and
21 and 22 (dust).
In order to guarantee a connection and disconnection in complete safety, the
SPeX receptacle is fitted with an electromechanical device (switch + ring) for
electrical interlocking with a contactor (breaker) and an integral pilot control
circuit.
Receptacle contacts are protected against standard test finger (IP2x/IPxxB)
according to IEC/EN 60529 standard.
WARNING
DANGER
result in serious injury or death. These instructions must be followed to
CAUTION
ensure the safe and proper installation, operation and maintenance of
the MELTRIC
NOTICE
power to the circuit to eliminate the risk of electrical shock. This product
must be installed with an electrical interlock that prevents connection or
ADVERTENCIA
disconnection in a loaded condition.
DANGER
n
RATINGS
CAUTION
AVISO
SPeX devices are provided with optional auxiliary contacts that make after
and break before the phase contacts. The ratings for auxiliary contacts are
shown in Table 1.
Device
SPeX
* Rating in not UL or CSA listed
n
INSTALLATION
SPeX must be installed by a qualified person in accordance with all
applicable local and national electric codes. Be sure power is off before
starting.
WARNING
DANGER
CAUTION
NOTICE
SPeX
ADVERTENCIA
The supply of the pilot circuit must be protected against transient over-voltages
DANGER
of 4 kV by means of an appropriate isolating device. Follow the requirements
set forth by the ATEx classification. DO NOT ATTEMPT TO TURN THE RING
CAUTION
TOWARDS ''1'' WHEN THE PLUG IS NOT ENGAGED.
AVISO
Electrical interlocking with a contactor is mandatory.
Assembly
WARNING
Insert cable through the cable gland and the handle or through the inclined
sleeve.
DANGER
Wiring of the pilot wires
CAUTION
Use flexible conductors with a cross-sectional area between 0.5 and 1 mm2
NOTICE
(16 to 20 AWG).
NOTICE: These conductors must be connected to the wires of the microswitch
ADVERTENCIA
by means of the isolated crimping lugs supplied. Use an appropriate crimping
DANGER
tool.
CAUTION
A typical pilot circuit wiring diagram is shown below.
AVISO
Wiring of the main conductor
Wire the main conductors within the amperage and hazardous duty
requirements of the ATEX (T5) classification. The cross-section must
be at least that defined in the certificate or the CE Declaration of Conformity,
WARNING
depending on the maximum current.
DANGER
Strip the conductor by 1.8" (46 mm). Crimp the threaded lug or the ferrule with
CAUTION
the appropriate die (NFC 20-130 or VDE 0220 or another). Hexagonal crimping
is recommended.
NOTICE
Tighten the threaded lug with a 24 mm wrench or tighten the ferrule with a screw
ADVERTENCIA
and a washer with a 19 mm wrench. Apply a torque ca. 95 ft-lbs (70 N.m).
DANGER
While tightening the ferrule, prevent the contact from rotating or transmitting
CAUTION
torque to the device with a 24 mm wrench.
AVISO
Assembly of the connector
Assemble the handles on the body of the products with the supplied gaskets
and screws and tighten the cable gland with an appropriate tool. To achieve
the IP65/IP66 of an interlocked connector, use a cable that incorporates the
two pilot wires that are required for the interlock, or use an ATEX cable gland
bushing that allows the passage of the main cable and the two pilot cables. The
silicone ring must be assembled on the receptacle ring.
Assembly of the metal inclined sleeve.
Maintain air and creepage distances when assembling the appliance inlet or the
receptacle onto the metal inclined sleeve, according to the operating voltage of
the main and auxiliary circuit and the degree of pollution.
The metal inclined sleeve must be grounded to Earth.
Assembly of the plug/inlet cap
WARNING
Place the lug located at the tip of the wire under one of the mounting screws
on the inlet side, or under the screw provided under the receptacle side.
DANGER
CAUTION
NOTICE
ADVERTENCIA
DANGER
CAUTION
AVISO
Color-coded rings
In order to achieve watertightness, do not forget the color-coded ring at the rear
of the inlet or receptacle.
Color-coded ring
The color-coded rings allows visual identification of the pole depending on the
color code of each country. Place the color coded gasket between the inlet or
receptacle and its rear accessory or panel.
Isolating ring
Flat gasket
When assembling the SPeX on a metallic support (enclosure, panel, etc.),
the isolating ring must be positioned as above. Be sure to use the black flat
gasket, which guarantees the watertightness, between the isolating ring and
the accessory.
Receptacles, plugs, connectors and inlets are protected against dust and water
ingress by means of caps, which must be re-assembled after use.
To achieve IP65/IP66, the receptacle or connector cap must be assembled with
its slot facing the socket-outlet protruding finger.
n
OPERATION
To ensure safe and reliable operation, MELTRIC
must be used in accordance with their assigned ratings.
WARNING
They can only be used in conjunction with mating receptacles or plugs
DANGER
manufactured by MELTRIC
the
CAUTION
NOTICE
ADVERTENCIA
DANGER
CAUTION
AVISO
1 Insert the plug straight into the receptacle, until a 'click' is heard. NOTICE:
The plug and its flexible cable must not exert constraint on the receptacle.
2 Pull on the plug to make sure it is properly latched in the receptacle.
A small rotation of the plug, in either direction, allows the locking finger of the
receptacle to prevent any further rotation.
3 To close the pilot circuit, turn the ring of the receptacle up to the stop
towards "1".Check the continuity of the pilot.
Do not attempt to turn the ring toward "1" when there is no plug engaged.
Defeating the mechanical lock could create a potentially hazardous or
explosive condition if energized under load.
WARNING
4 To open the pilot circuit and unlock the plug, turn the ring back to "0" up
DANGER
to the stop. Press on the button to release the plug. The caps must then be
CAUTION
re-assembled on both sides.
NOTICE
ADVERTENCIA
DANGER
CAUTION
AVISO
n
MAINTENANCE
WARNING
DANGER
eliminate the risk of electrical shock. Rules applying to products for use in
explosive atmospheres impose that any replacement of component must be
CAUTION
performed under the control of the manufacturer: MELTRIC
NOTICE
®
MELTRIC
products require little on-going maintenance. However, it is a good
ADVERTENCIA
practice to periodically perform the following general inspections:
DANGER
CAUTION
• Check the mounting screws for tightness.
AVISO
• Verify that the weight of the cable is supported by the strain relief mechanism
and not by the terminal connections.
• Check the IP gaskets for wear and resiliency. Replace as required.
• Verify the electrical continuity of the ground circuit.
• Check the contact surfaces for cleanliness and pitting.
Use a clean cloth to rub off deposits of dust or similar foreign materials on the
contacts and the plug interiors. Sprays should not be used, as they tend to
collect dirt. If any significant pitting of the contacts or other serious damage is
observed, the device should be replaced.
Any repair or service must be achieved with genuine
n
MANUFACTURER'S RESPONSIBILITY
®
MELTRIC
responsibility is strictly limited to the repair or replacement of
any product that does not conform to the warranty specified in the purchase
contract. MELTRIC
damages associated with the loss of production, work, profit or any financial
loss incurred by the customer.
®
MELTRIC
Corporation shall not be held liable when its products are used in
conjunction with products not bearing the
The devices that are not marked with the
shall void all warranties on the product.
®
MELTRIC
Corporation is an ISO 9001 certified company. Its products
are designed, manufactured and rated in accordance with applicable UL,
CSA, NOM and IEC standards. MELTRIC
its products in accordance with Marechal keying standards established to
ensure intermatablility with similarly rated products manufactured by Marechal
Electric Group.
Nous /
We
MARECHAL ELECTRIC S.A.S.
5, avenue de Presles
F-94417 SAINT-MAURICE Cedex – France
Tel :
+33 (0)1 45 11 60 00
Fax :
+33 (0)1 45 11 60 60
E-mail : contact@marechal.com
Déclarons sous notre seule responsabilité que le produit /
Type
Type
SPeX
Intensité /
Section /
Current
A
235
290
335
415
376
456
415
493
450
530
497
570
584
540
620
600
680
:
Une étude comparative des normes: EN 60079-0 (versions 2018, 2012 + A11:2013 et 2009), EN 60079-7 (2007 et 2015) et EN 60079-31 (2014 et 2009) montre que le matériel
(*)
n'est pas concerné par les modifications substantielles.
A comparative study of the standards: EN 60079-0 (version 2018, 2012 + A11: 2013 and 2009), EN 60079-7 (2007 and 2015) and EN 60079-31 (2014 and 2009) shows that
the products are not concerned by the substantial modifications.
Satisfont aux dispositions des Directives du Conseil n° :
Satisfy the measures set in the Council Directives n°:
N° de notification de l'évaluation relatif à la qualité : LCIE 00 ATEX Q 8001 selon l'Annexe IV réalisé par l'organisme notifié n° 0081 :
LCIE – 33, avenue du Général Leclerc – 92260 Fontenay-Aux-Roses – France
Quality Assessment Notification Number: LCIE 00 ATEX Q 8001 according to Annex IV carried out by Notified Body N° 0081:
LCIE – 33, avenue du Général Leclerc – 92260 Fontenay-Aux-Roses – France
MARECHAL ELECTRIC S.A.S. au capital de 5 341 400 € - SIRET 552 149 577 00058 - NAF 2733Z – N° TVA FR16552149577
5, avenue du chemin de Presles 94410 Saint-Maurice FRANCE - +33 (0)1 45 11 60 00 -
A manufacturer of products using Marechal technology
MODE D'EMPLOI
INSTRUCCIONES
There are inherent dangers associated with electrical
products. Failure to follow safety precautions can
®
devices. Before installation, disconnect all sources of
Table 1 - Auxiliary Contact Ratings
120 VAC
-
Table 2 - Wiring Terminal Capacity
Main Contacts
Max
750 MCM
L1
L2
L1
L2
L1
L2
L1
L2
Isolating ring
®
or another licensed producer of products bearing
technology trademark.
Before inspecting, repairing, or maintaining MELTRIC
products, disconnect electrical power to the receptacle to
®
shall not be liable for any penalties or consequential
Declare under our sole responsibility that the product:
Connecteur unipolaire de puissance /
Marquage
Marking
II 2 G D
Ex e IIC T Gb, Ex tb IIIC T Db
LCIE 07 ATEX 6073 X
Section
Classe de température pour /
mm²
-20°C ≤ Ta ≤ + 40°C
T6
70
T5
T6
95
T5
T6
120
T5
T6
150
T5
T6
185
T5
T6
240
T5
T5
T6
300
T5
T6
400
T5
240 VAC
6 A (220 max)*
Min
2/0
L3
N
L3
N
L3
N
L3
N
Color-coded ring
®
designs and manufactures
Déclaration UE de Conformité
EU Declaration of Conformity
Single-pole power Connector
Caractéristiques d'étanchéité
Watertightness characteristics
IP65/IP66
GAZ /
GAS
Temperature class for:
-20°C ≤ Ta ≤ + 60°C
T5
/
T5
/
T5
/
T5
/
T5
/
T5
/
T4
T5
/
T5
/
2014/34/UE du 26 février 2014 (ATEX)
2011/65/UE + amendement n°2015/863 du 31/03/2015 (RoHS)
2014/34/EU dated February 26, 2014 (ATEX)
2011/65/EU + amendment no 2015/863 dated 2015/03/31 (RoHS)
Saint-Maurice, 2019-10-25
Anne LE GUENNEC
Responsable Produits Ex /
contact@marechal.com
480 VAC
-
Aux. Contacts
12-14 AWG
P1
P2
P1
P2
®
plugs and receptacles
®
Corporation.
technology trademark.
technology trademark
Conforme aux normes suivantes
Complies with the following standards
EN IEC 60079-0 : 2018(*)
EN 60079-7 : 2015 (*)
EN 60079-31 : 2014 (*)
POUSSIERES /
DUST
Température de surface /
Surface temperature for:
-20°C ≤ Ta ≤ + 40°C
-20°C ≤ Ta ≤ + 60°C
T56°C
T76°C
T56°C
T56°C
T76°C
T56°C
T56°C
T76°C
T56°C
T56°C
T76°C
T56°C
T56°C
T76°C
T56°C
T56°C
T76°C
T56°C
T59°C
T79°C
T56°C
T76°C
T56°C
T56°C
T76°C
T56°C
Manager of Ex-Proof Product
Back to Top
p
INSSPEX E
600 VAC
-
®
parts only.
/
/
/
/
/
/
/
/
INSSPEX E