18: Display setting for autonomy time
Interface
19: Acceptable input voltage range setting
Interface
00: Exit setting
Interface
Disconnect AC input and wait until the LCD display is off. The new setting will be activated when turning
on the UPS again.
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Ligne directe – Tél + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 07 19 AA 59 203 14
Setting
Parameter 2: Set up the display setting for autonomy time
EAT: If EAT is selected, it will display the remaining
autonomy time. (Default)
RAT: If RAT is selected, it will show accumulated autonomy
time so far.
Setting
Parameter 2: Set the acceptable high voltage point and
acceptable low voltage point for input voltage range by
pressing the Down key or Up key.
HLS: Input high voltage point
For 200/208/220/230/240 VAC models:
280/290/300: setting the high voltage point in parameter 2.
(Default: 300Vac)
For 100/110/115/120/127 VAC models:
140/145/150: setting the high voltage point in parameter 2.
(Default: 150Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
110/120/130/140/150/160: setting the low voltage point in
parameter 2. (Default: 110Vac)
For 100/110/115/120/127 VAC models:
55/60/65/70/75/80: setting the low voltage point in
parameter 2. (Default: 55Vac)
Setting
Exit the setting mode.
73