Drain Piping Work
Flexible Hose
Pipe Clamp
Indoor
Unit
Panel
Drain Test
Feed Water
Flexible Drain Hose
NOTE
This Indoor Unit uses a drain pump for condensed water drainage. Install the unit horizontally to prevent water leakage
or condensation around the air outlet.
Panel Installation
•
The front panel can only be fitted in one direction, follow the piping direction. (Follow piping arrow sticker on front panel)
•
Be sure to remove the installation template before installing the front panel.
•
Open the air intake grille by pulling back the catchers and removing it together with filter from panel.
•
Install the front frame panel onto the indoor unit by 4 screws and tighten it completely to prevent cool air leakage.
•
Connect the LED wire and air swing wire to the indoor unit.
•
The air swing connector must put inside the control box after connected.
Ceiling
Main Drain Pipe
Open
From
Front
Panel
Air Swing Wire
•
Drain pipe must be in downward gradient for smooth
drainage.
•
Avoid installing the drain pipe in up and down slope
to prevent reversed water flow.
•
During the drain pipe connection, be careful not to exert
extra force on the drain connector at indoor unit.
•
The outside diameter of the drain connection at the
flexible drain hose is 20mm.
•
Be sure to execute heat insulation (polyethylene foam
with thickness more than 8.0mm) on the drain piping to
avoid the condensed water dripping inside the room.
•
Connect the main drain pipe to the flexible drain.
•
Feed water from flexible drain hose to check the piping
for leakage.
•
When the test is completed, connect the flexible drain
hose to the drain connector on the indoor unit.
LED Wire
From
Unit
Control
Box
1-5
Screw