According to UL 60947-4-1
Use wire Cu 75
only.
CA9-190, CA9-205: Use Pressure Terminal Connectors ILSCO D-3608 (Sprecher + Schuh ref CA9-TS205L) or use Listed (ZMVV/7) Wire
Connectors and Soldering Lugs. Wire connectors (Cable pole-shoe) crimped with special factory tool. Enclosure
with min dimension 24 by 20 by 10 inches should be used. Suitable for use on a circuit capable of delivering not more
than the max symmetrical amperes at the max voltage shown in table 1 and 3 below.
CA9-265, CA9-305, CA9-370: Use Pressure Terminal Connectors ILSCO D-3615 (Sprecher + Schuh ref CA9-TS370L) or use Listed (ZMVV/7)
Wire Connectors and Soldering Lugs. Wire connectors (Cable pole-shoe) crimped with special factory tool. Enclosure
with min dimension 36 by 30 by 12 inches should be used. Suitable for use on a circuit capable of delivering not more than
the max symmetrical amperes at the max voltage shown in table 2 and 4 below.
Type 1
CA9-190, CA9-205
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 208-240V (kA)
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
CA9-265, CA9-305, CA9-370
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 208-240V (kA)
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
Type 2
CA9-190, CA9-205
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
CA9-265, CA9-305, CA9-370
Circuit Breaker A
Fuse A/Class
Max Short Circuit Current at 480V (kA)
Max Short Circuit Current at 600V (kA)
For applications above 690V, terminal shrouds CA9-TS205L or CA9-TS370L should be used.
Sprecher + Schuh maintains current product environmental information on its website at http://www.sprecherschuh.com/library/approvals/compliance.html
Sprecher + Schuh, 15910 Int. Plaza Dr., Houston TX 77032, USA
Publication CA9-IN002E-EN-E January, 2022
Table 1
140G-K/J
140G-K3
400/RK5
400/J
10
100
100
10
100
35
10
100
25
Table 2
140G-M
140G-M5 140G-M6 140G-M0
800/L
600/J
10
100
100
18
100
50
18
100
25
Table 3
140G-K
140G-K6
350/J
400/J
10
100
65
10
100
35
Table 4
140G-M
140G-M6
600/J
600/J
100
18
65
100
18
35
140G-K6
140G-K0
140G-K15
140G-J2
100
100
100
65
100
100
35
65
100
100
100
65
100
35
42
Breaking all lines. Max 600V AC, 50/60 Hz:
Herm ref comp, AC-8a
TYPE
FLA
LRA
200
CA9-190
1400
CA9-205
250
1500
CA9-265
300
2100
CA9-305
350
2450
CA9-370
520
3120
140G-J3
140G-J6
140G-J0
65
100
100
100
25
35
65
100
18
22
25
Ballast, AC-5a/
Elevator duty
Resistance air heating
77
250
99
300
125
400
450
149
156
520
DIR 10002941925 (Version 05)
Copyright © 2022 Sprecher+Schuh, Inc. All Rights Reserved. Printed in Sweden.
4/4