Télécharger Imprimer la page

Honeywell TP30WK Mode D'emploi page 26

Déshumidificateur portatif et déshumidificateur portatif intelligent
Masquer les pouces Voir aussi pour TP30WK:

Publicité

Les langues disponibles

Les langues disponibles

ERROR CODE GUIDE
CODE
POSSIBLE CAUSE
Water tank not installed
P1
or positioned correctly
EH
Humidity sensor failure
Temperature
E1 / E2
sensor failure
Refrigeration System
E3
Protection
Abnormal Pumping
E5
Drainage
POSSIBLE SOLUTIONS
This only appears for model TP70PWK / TP70PWKN /
TP70PWKNR with Built-in Drain Pump. Position the water
tank correctly into the unit. Unit will not operate until the
water tank is secured in the correct position.
Please contact the service center.
Please contact the service center.
If E3 appears, check if the ambient room temperature
o
has exceeded 89.6
F (32
until the room ambient temperature has reduced to
o
o
below 86
F (30
C) for at least 2 hours, or try to remove the
unit to a cooler room for at least 2 hours before running
dehumidification mode again.
If the E3 appears again in 2 hours, please contact the
service center.
Check that Auto Drain Pump Tube and Auto Drain Pump
Cap is connected and properly installed onto the Drain
Outlet.
Check the seal washer (transparent) in drain tube cap is
properly installed in side.
Check that the Direct Drain Outlet is clean and not jammed
by sediments collected on and around the outlet.
Check to see that the correct Auto Drain Tube is being used
(the dehumidifier comes with a 16ft/ 5m long Auto Drain
Pump Tube. The tube should not be longer than 16ft/ 5m.
Check that the Auto Drain Pump Cap is securely screwed
onto the Drain Outlet and no leakage is occurring due to
unsecure connection.
If all checking is satisfied,unplug the dehumidifier and
drain off water in bucket manually then plug the products
to run again.
If E5 appear again,please contact the consumer service
center.
EN
25
o
C). If yes, the unit may not run

Publicité

loading