Installation distances
C596
Combustible roof
495
INSTALLATION AGAINST COMBUSTIBLE WALLS
Permitted area for
combustible parts
of the building
400
500
* If the stove is placed on a hearth plate made of glass for example (accessory), the height from the floor is affected by a distance corresponding to the thickness of the hearth plate, for a free standing
glass hearth plate this is 10 mm.
** To prevent discolouration of painted non-flammable walls we recommend that the same side distance as to combustible walls is used.
WHEN INSTALLING TURNTABLE (OPTION) the fol-
lowing installation distances do not apply.
See the separate turntable installation instructions.
!
A separate glass hearth
plate (accessory) increases
the connection height to
the chimney by 10 mm.
400
Combustible wall
695
Combustible wall
750
440
140
Ø150
35
Air inlet Ø67
100
INSTALLATION AGAINST FIREWALLS
800
Fire-retardant wall of
brick or concrete
545
850
Fire-retardant wall of
brick or concrete
200**
450**
The minimum distance in front of
the stove opening to combustible
parts of the building or interior
decoration must be at least 1 m.
The dimension diagrams only
show the minimum permitted
installation distances for the
stove. When connecting to a steel
flue, also note the safety distance
requirements of the flue. The
safety distance between an un-
insulated flue and a combustible
part of the building should be at
least 450 mm.
A = height from floor to chimney
connection upwards
B = height from floor to c/c chimney
connection rear
C = height from floor to air inlet
D = height from floor to lower edge
of hatch