No cooling
None of the components operate
- Unit is not supplied with voltage > Ensure that doors and switches are closed
Compressor, condenser fan and evaporator fan operate
- No refrigerant in the cooling system > Consult the refrigeration engineer or the häwa GmbH technical support
- Mechanical fault > Consult the refrigeration engineer or the häwa GmbH technical support
Compressor and external fan operate, internal fan does not operate
- Faulty fan capacitor > Replace the capacitor of the fan
- Faulty evaporator fan > Replace the faulty fan
External and internal fan operate, compressor does not operate
- Faulty thermal overload protector (if present)
- Faulty relay or compressor-starting PTC > Replace relay or compressor-starting PTC
- Faulty capacitor for compressor starting (if present) > Replace capacitor
- Faulty compressor motor > Consult the refrigeration engineer or the häwa GmbH technical support
- Faulty high-pressure switch > Consult the refrigeration engineer or the häwa GmbH technical support
- Faulty compressor remote switch (if present) > Replace the remote switch
Internal fan, external fan and compressor operate
- Adjusting thermostat faulty or set at a higher temperature than the temperature in the cabinet
> Replace the thermal overload protector and check the efficiency of the electrical compressor components