Télécharger Imprimer la page

elgris SMART METER LAN Mode D'emploi page 14

Publicité

9.1
Représentation au registre général
La première adresse de registre est 40000 et les registres peuvent être lus à l'aide de la fonction
0x03.
Address Size Name
40000
2
ID
40002
1
DID
40003
1
L
40004
16
Mn
40020
16
Md
40036
8
Opt
40044
8
Vr
40052
16
SN
9.2
Représentation du registre Modèle de compteur WYE Connect
Address Size
40069
1
40070
1
40071
1
40072
1
40073
1
40074
1
40075
1
40076
1
40077
1
40078
1
40079
1
40080
1
40081
1
PhVphAB
40082
1
PhVphBC
40083
1
PhVphCA
40084
1
40085
1
40086
1
40087
1
40088
1
40089
1
40090
1
40091
1
Label
Value Type R/W
Common
SunSpec_DID
SunSpec_Length
Manufacturer
Model
Options
Version
Serial Number
Name
Label
WYE-connect
ID
three phase
(abcn) meter
L
SunSpec_Length
A
Amps
AphA
Amps Phase A
AphB
Amps Phase B
AphC
Amps Phase C
A_SF
PhV
Voltage LN
PhVphA
Voltage AN
PhVphB
Voltage BN
PhVphC
Voltage CN
PPV
Voltage LL
V_SF
Hz
Hz
Hz_SF
W
Watts
WphA
Watts phase A
WphB
Watts phase B
WpbC
Watts phase C
W_SF
Value = "SunS" (0x53756e53).
1
uint32
R
Uniquely identifies this as a
SunSpec MODBUS Map
Value = 0x0001. Uniquely identifies
1
uint16
R
this as a SunSpec Common Model
Block
65 = Length of block in 16-bit
65
uint16
R
register
string
R
"elgris"
string
R
"SMART METER"
String
R
Not used, for future compatibility
string
R
"1.10.15"
string
R
19000XXXX (SMA serial compliant)
Value Type R/W
1
uint16
105
uint16
int16
int16
int16
int16
sunssf
int16
int16
int16
int16
int16
uint16
uint16
uint16
sunssf
int16
sunssf
int16
int16
int16
int16
sunssf
Description
Description
Value = 203
Uniquely identifies this
R
as a
SunSpec 203 MODBUS
Map
105 = Length of block in
R
16-bit register
R
Total AC current
R
Phase A current
R
Phase B current
R
Phase C current
R
Current scale factor
Line to neutral AC
R
voltage
R
Phase voltage AN
R
Phase voltage BN
R
Phase voltage CN
R
Line to Line AC voltage
R
Line voltage AB
R
Line voltage BC
R
Line voltage CA
R
Voltage scale factor
R
Frequency
R
Frequency scale factor
R
Total real power
R
Real power phase A
R
Real power phase B
R
Real power phase C
R
Real power scale factor

Publicité