Natural Gas - CDV155D, CDV255D, CDV305D
!
WARNING: If the information in these
instructions is not followed exactly, a fire or
explosion may result causing property damage,
personal injury or loss of life.
— Do not store or use gasoline or other flammable
vapors and liquids in the vicinity of this or any
other appliance.
— WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use
any phone in your building.
• Immediately call your gas supplier from a
neighbor's phone. Follow the gas supplier's
instructions.
• If you cannot reach your gas supplier, call the
fire department.
— Installation and service must be performed by
a qualified installer, service agency or the gas
supplier.
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
!
WARNING: This product can expose you to chemicals including epichlorohydrin
which is known to the State of California to cause cancer and birth defects and/or
other reproductive harm. For information go to www.p65warnings.ca.gov.
The appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home,
where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This
appliance is not convertible for use with other gases, unless a certified kit is used.
Cozy Heating Systems, LLC | cozyheaters.com | 888-444-1212 | 250 West Laurel Street | Colton, CA 92324
Installation and Operating Instructions
WALL FURNACE
|
Propane Gas - CDV156D, CDV256D, CDV306D
- The coating selected to provide longer life to
- Installation, maintenance, service, troubleshooting
- This unit is for residential use only and is not
Page 1
DIRECT VENT
CDV25-D
CDV30-D
CDV15-D
!
WARNING: Improper installation, adjustment,
alteration, service or maintenance can cause
injury or property damage. Refer to this manual
for proper installation. For assistance or for
additional information consult a qualified installer,
service agency or the gas supplier.
the heat exchanger may smoke slightly upon
initial firing. Provide adequate ventilation if
this occurs.
& repairs must be performed by a qualified
service agency. DO NOT attempt any of these
procedures if you are not qualified as this could
expose you to property damage, personal injury,
or loss of life and will invalidate all warranties.
approved for installation in greenhouses, or
environments involving dusty, wet, corrosive, or
explosive conditions. Such conditions will invalidate
the warranty and may create unsafe conditions.
1019061-B

Publicité

loading

Sommaire des Matières pour COZY CDV25-D

  • Page 1 This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used. Cozy Heating Systems, LLC | cozyheaters.com | 888-444-1212 | 250 West Laurel Street | Colton, CA 92324 Page 1...
  • Page 2 CONTENTS READ CAREFULLY BEFORE INSTALLING UNIT Before Installation These installation instructions are a general guide and do not supersede applicable local codes and ordinances. Before planning Standards ........... 2 or making the installation be sure it complies with all phases of the Specifications ........
  • Page 3 SPECIFICATIONS & DIMENSIONS Your Direct Vent Wall Furnace is shipped complete in one carton. This carton contains the furnace, vent cap, vent tube, air inlet tube, template with rough-in dimensions, installation and operating instructions, and the thermostat with thermostat wire. NOTE: There will be two cartons if an optional vent kit or blower is purchased.
  • Page 4 SAFETY - Continued It is imperative that control compartments, burner, and 20. If it is suspected that rising water may enter the furnace, circulating air passageways of the furnace be kept clean. turn off the gas immediately. Do not use this appliance if any part has been under water.
  • Page 5 CLEARANCES Inside F IX E D Corner B L E C L O S E O P E R A Detail F IX E D C L O S E = Vent Terminal = Air Supply Inlet = Area where terminal is not permitted CANADIAN REFERENCE LETTER TO DRAWING...
  • Page 6 Min. 12” Minimum 1/2” Floor 4” Floor CDV15-D CDV25-D / CDV30-D ALL VENT CAPS SPECIAL PRECAUTIONS LOCATION Due to high temperatures the appliance should be located out of 1) The wall furnace must be installed on an outside wall. traffic and away from furniture and draperies.
  • Page 7 INSTALLATION WARNING: Failure to follow these instructions carefully could result in poor performance, property damage, personal injury or death. STEP 1. LOCATE VENT OPENING Locate wall studs and center 9” vent opening a minimum of 22” for CDV15 or 24-1/8” for CDV25/30 above the floor. To locate furnace at minimum clearance from floor, remove template from carton and set on floor at location desired.
  • Page 8 INSTALLATION FOR ALTERNATE WALL DIMENSIONS 9” TO 15" WALLS 15” TO 24” WALLS 9” TO 15” WALLS ( CDV15 / CDV25-D ) ( CDV15 / CDV25-D ) ( CDV30-D ) For 9" to 15" wall use Vent Kit No. For 15" to 24" wall use only Vent Kit For 9” to 15” wall use Vent Kit No. VK30/9- VK1525/9-15-B.
  • Page 9 INSTALLATION FIG. 4 CDV15-D CDV25/30-D 18" Cabinet 34-1/2" Cabinet 9” Dia. 9" Dia. Opening Opening 9" Valve 29-3/4" 13-3/8" 16-5/8" Inlet 31-3/4" 22" 24-1/8" Valve Inlet 8" 13” 1/2" Floor 4” Shut Off Valve 1/8” N.P.T. 1/2” Min. Center Floor Pressure Tap Line Pipe Elbow Supply...
  • Page 10 INSTALLATION FIG. 7 Wall Stud Inside Wall Wall Thimble Extension Wall Thimble Assembly Outside Wall Vent Terminal Spacer Plate Vent Terminal GAS CONNECTION FIG. 8 This heater must be connected to a gas supply capable of supplying the full rated capacity. Provide a 1/8 inch N.P.T. TO HEATER GAS plugged tapping, accessible for test gauge connection, CONTROL VALVE...
  • Page 11 LIGHTING INSTRUCTIONS MODELS: CDV155D / CDV156D / CDV255D / CDV256D / CDV305D / CDV306D FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: This appliance has a pilot which must be • If you cannot reach your gas supplier, call If you do not lighted by hand.
  • Page 12 MAINTENANCE WARNING: This is a gas-fired appliance. Keep the area clear of gasoline and other flammable vapors and liquids. All combustible material must be kept clear of this area to avoid fire or explosion. For proper and safe operation keep furnace and furnace If the air intake tube or the exhaust tube is removed, follow area clean. At regular intervals turn control valve to off, Step 3 of the installation section for re-assembly. Be sure to let cool and clean inside control compartment and under check gaskets and replace if there is any sign of damage.
  • Page 13 MAINTENANCE BURNER ORIFICE Fig 11: Specific Elevations This appliance is orificed at the factory for elevations up Model 0 to 2,000’ - 4,000’ - 6,000’ - 8,000’ - 2,000’ 4,000’ 6,000’ 8,000’ 10,000’ to 2,000 ft. If installed above 2,000 ft., the BTU input must be reduced 4% per 1,000 ft.
  • Page 14 MAINTENANCE Label all wires prior to disconnection when servicing controls. Wiring errors can cause CAUTION: improper and dangerous operation. Verify proper operation after servicing. NOTE: The furnace and all components must be inspected at least annually by a qualified service technician. This should include the burner, heat exchanger, and vent system. Be sure that the flow of combustion and ventilation air are not obstructed. FIG.
  • Page 15 TROUBLESHOOTING CHART ( FOR QUALIFIED SERVICE TECHNICIAN ) SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION Flame 1. Defective operator section of valve. 1. Replace valve. Too Large 2. Burner orifice too large. 2. Check with local gas company for proper orifice size and replace. 3. See burner orifice section, Page 13. 3.
  • Page 16 DVB-3 BLOWER KIT INSTALLATION - ( OPTIONAL ) This kit must be installed by a qualified installer or service technician only. Compatable with CDV15-D / CDV25-D / CDV30-D Series. CAUTION: Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
  • Page 17 DVB-3 BLOWER KIT INSTALLATION - ( OPTIONAL ) This kit must be installed by a qualified installer or service technician only. Compatable with CDV15-D / CDV25-D / CDV30-D Series. FIG. 15-A LADDER PART DESCRIPTION PART NO. SCHEMATIC BLOWER HOUSING w/ Motor & Blower 70201 JUNCTION 43610 JUNCTION BOX COVER...
  • Page 18 BBSK INSTALLATION INSTRUCTIONS - ( OPTIONAL ) This kit must be installed by a qualified installer or FIG. 16-A service technician only. 13/16" CDV15 STEP 1. Find the drilling location at the rear of the cabinet, near the top. See Figure 16-A. 3-1/4" STEP 2. Drill a ½”...
  • Page 19 BBSK-CDV LIGHTING INSTRUCTIONS - ( OPTIONAL ) FOR YOUR SAFETY READ BEFORE LIGHTING WARNING: This appliance has a pilot which must be • If you cannot reach your gas supplier, call If you do not lighted by hand. When lighting the pilot, the fire department. follow these follow these instructions exactly.
  • Page 20 DIRECT VENT WALL FURNACE PARTS LIST Natural Gas: CDV155D | Propane Gas: CDV156D = 6-3/4” Dia. = 4-3/16” Dia. OPTIONAL VENT EXTENSIONS VK1525/9-15 Vent Kit Assembly VK1525/15-24 Vent Kit Assembly OPTIONAL BLOWER ASSEMBLY / DVB-3 DVB3 Blower Kit also includes: 43078 Cover Plate 43625 Blower Shield for CDV25/30 NOTE: Parts &...
  • Page 21 DIRECT VENT WALL FURNACE PARTS LIST Natural Gas: CDV155D | Propane Gas: CDV156D ATTN: Contractors and Qualified Service Technicians: We only sell parts through our wholesalers. For prompt parts service, contact the wholesaler from which you purchased your Cozy heater. PART DESCRIPTION PART DESCRIPTION PART NO.
  • Page 22 DIRECT VENT WALL FURNACE PARTS LIST Natural Gas: CDV255D & CDV305D | Propane Gas: CDV256D & CDV306D = 6-3/4” Dia. = 4-3/16” Dia. Ref No. 61, 62 & 63 Not Illustrated. OPTIONAL VENT EXTENSIONS VK1525 / 9-15 & VK30 / 9-15 Vent Kit Assembly VK15/25 / 15-24 Vent Kit Assembly OPTIONAL BLOWER ASSEMBLY / DVB-3...
  • Page 23 ATTN: Contractors and Qualified Service Technicians: We only sell parts through our wholesalers. For prompt parts service, contact the wholesaler from which you purchased your Cozy heater. Natural Gas Model Numbers ..
  • Page 24 RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS AND ARE IN LIEU OF ALL OTHER REMEDIES. WHICH VARY FROM STATE TO STATE. TO REGISTER YOUR FURNACE: GO ONLINE TO THE COZY HEATERS WEBSITE AT: www.cozyheaters.com/warranty-registration/ COZY HEATING SYSTEMS, LLC 250 WEST LAUREL STREET – COLTON, CA 92324...
  • Page 25 No es posible hacerlo funcionar con ningún otro tipo de gas, a menos que se use un kit (juego) certificado. Cozy Heating Systems, LLC | cozyheaters.com | 888-444-1212 | 250 West Laurel Street | Colton, CA 92324 Manual Español Página 1...
  • Page 26 TABLA DE CONTENIDO LEA ESTA SECCIÓN ANTES DE INSTALAR LA UNIDAD Antes de la Instalación Este instructivo es una guía general para su aparato y no substituye los códigos y reglamentos locales que aplican. Antes de planear o Las Normas ........2 realizar la instalación, asegúrese de que cumple con todas las fases Especificaciones .........
  • Page 27 ESPECIFICACIONES DEL CALEFACTOR Su calefacción de pared con ventilación directa es embalada completa en un solo cartón. Este cartón contiene la calefacción, tapa para ventilación, tubo de ventilación, tubo de entrada de aire, plantilla con dimensiones, instrucciones de instalación y operación, y el termostato con cable de termostato.
  • Page 28 REGLAS DE SEGURIDAD - Continuado técnico de servicio calificado. Quizá sea necesario limpiar 20. Si se sospecha que el nivel de agua puede liegar a penetrar el horno, cierre el gas inmedíatamente. No use este aparato con más frecuencia el aparato debido a un exceso de pelusa si alguna de sus partes se ha sumergido en agua.
  • Page 29 ESPACIOS LIBRES Detalle de F IJ O la Esquina B L E O P E R A C E R R A F IJ O Interior C E R R A = Terminal de Ventilación = Entrada de Suministro de Aire = Área Donde no se Permite el Terminal Instalaciones...
  • Page 30 1.27cm Piso 10.16cm Piso Todos los Casquillos del Respiradero CDV15-D CDV25-D / CDV30-D PRECAUCIONES ESPECIALES UBICACIÓN El calefactor de pared debe instalarse Debido a las altas temperaturas, el electrodoméstico debe ubicarse en una pared que dé al exterior. fuera del tráfico y lejos de muebles y cortinas.
  • Page 31 INSTALACIÓN PRECAUCIÓN: El incumplimiento de estas instrucciones con cuidado puede provocar un rendimiento deficiente, daños a la propiedad, lesiones personales o la muerte. PASO 1. UBICACIÓN DE APERTURA PARA LA VENTILA. Ubique los pernos de la pared y centre la abertura de ventilación de 9”, como mínimo, 22” para CDV15 o 24-1/8” para CDV25/30 sobre el piso.
  • Page 32 PAREDES DE 22.86 CM A 38.10 CM PAREDES DE 38.10 CM A 60.96 CM CALEFACTOR PAREDES DE ( CDV15 / CDV25-D ) (CDV15 / CDV25-D) 22.86 CM A 38.10 CM (CDV30-D) Para paredes de 22.86 cm a 38.10 cm, utilice El VK1525/15-24-B se utiliza con los modelos Para paredes de 22.86 cm a 38.10 cm, utilice el...
  • Page 33 INSTALACIÓN Illustración 4 CDV15-D CDV25/30-D 45.72 cm 87.63 cm Gabinete Gabinete Apertura Apertura del diametro del diametro 22.86 cm 22.86 cm Entrada 22.86 de Valvula 71.76cm 33.97 42.23 de Gas 80.65cm 55.88cm Entrada 61.28cm de Valvula 20.32 de Gas 33.02cm Llave de 1.27cm Presión de...
  • Page 34 INSTALACIÓN Illustración 7 Entramado de la Pared Pared Interior Extension del Guardacabo de la Pared Calefactor Ensamble del Guardacabo de la Pared Pared Exterior Placa Espaciadora para la Terminal de la Ventila Terminal de Ventila Conexión del Gas Illustración 8 Este calentador debe estar conectado a un suministro de gas capaz de suministrar la capacidad nominal completa.
  • Page 35 INSTRUCCIONES DE ENCENDIDO MODELOS: CDV155D / CDV156D / CDV255D / CDV256D / CDV305D / CDV306D PARA SU SEGURIDAD LEA ESTE INSTRUCTIVE ANTES DE ENCENDER EL APARATO ADVERTENCIA: Este aparato tiene un piloto que se debe encender compañia de gas. • Si no se puede comunicar con la compañía de gas, a mano.
  • Page 36 MANTENIMIENTO ADVERTENCIA: ESTE APARATO FUNCIONA A GAS. MANTENGA EL ÁREA LIBRE DE GASOLINA Y DE OTROS VAPORES Y LÍQUIDOS INFLAMABLES. TODO MATERIAL COMBUSTIBLE SE DEBE MANTENER ALEJADO DE ESTA ÁREA PARA EVITAR QUE HAYA INCENDIOS O EXPLOSION. Para que su calefactor tenga un funcionamiento apropiado y No obstruya el paso del aire para combustión y ventilación.
  • Page 37 MANTENIMIENTO ESPREAS DEL QUEMADOR Illustración 11: ELEVACIÓN ESPECÍFICA Este aparato viene con las espreas del quemador de Números 609.61 a 1219.21 a 1828.82 a 2438.43 a de Model 609.61m 1219.21 m 1828.82 m 2438.43 m 3048.04 m fábrica para elevaciones de hasta 609.61 metros. Si se instala por encima de una elevación de 609.61 metros, la GAS NATURAL entrada del BTU se debe reducir 4% por 304.80 metros.
  • Page 38 MANTENIMIENTO Etiquete todos los cables antes de la desconexión al realizar el mantenimiento de PRECAUCIÓN: los controles. Los errores de cableado pueden causar un funcionamiento incorrecto y peligroso. Verificar el funcionamiento correcto después del servicio. NOTA: El calefactor y todos los componentes se deben inspeccionar por lo menos usa vez al año por un técnico de servicio calificado.
  • Page 39 TABLA DE LOCALIZACIÓN DE PROBLEMAS ( Para ser usado por un instalador o un técnico de servicio calificados. ) SÍNTOMA CAUSAS POSIBLES ACCÍON CORRECTIVA LA LLAMA ESTÁ 1. Sección defectuosa de la válvula. 1. Cambie la válvula. MUY GRANDE 2. Esprea del quemador demasiado grande. 2.
  • Page 40 INSTRUCCIONES DE INSTALACION PARA EL KIT DEL SPOLADOR DVB-3 - ( OPCIONAL ) Este kit solo debe instalarlo un instalador calificado o un técnico de servicio. Compatible con la serie CDV15-D / CDV25-D / CDV30-D. PRECAUCIÓN: Etiquete todos los cables antes de la desconexión al realizar el mantenimiento de los controles.
  • Page 41 INSTRUCCIONES DE INSTALACION PARA EL KIT DEL SPOLADOR DVB-3 - ( OPCIONAL ) Este kit solo debe instalarlo un instalador calificado o un técnico de servicio. Compatible con la serie CDV15-D / CDV25-D / CDV30-D. Illustración 15-A ESQUEMA DESCRIPCIÓN DE LA PARTE NÚM.
  • Page 42 INSTRUCCIONES PARA LA INSTALACIÓN DEL KIT BBSK - ( OPCIONAL ) Este kit solo debe instalarlo un instalador calificado o un Illustración 16-A técnico de servicio. 2,06375cm CDV15 PASO 1. Encuentre la ubicación de perforación en la parte posterior del gabinete, cerca de la parte superior.
  • Page 43 INSTRUCCIONES DE ENCENDIDO PARA EL MODELO BBSK - ( OPCIONALES ) PARA SU SEGURIDAD LEA ESTE INSTRUCTIVO ANTES DE ENCENDER EL APARATO ADVERTENCIA: SI NO Este aparato tiene un piloto que se debe encender • Si no puede comunicarse con la compañía de gas, SIGUE ESTAS a mano.
  • Page 44 LISTA DE PIEZAS - DE HORNO DE PARED DIRECTA Gas Natural: CDV155D | Gas Propano: CDV156D = 17.145 cm Dia. = 10.6299 cm Dia. EXTENSIONES OPCIONALES DEL RESPIRADERO VK1525/9-15 Juego para el Ensamble de la Ventila VK1525/15-24 Juego para el Ensamble de la Ventila MONTAJE DEL VENTILADOR OPCIONAL / DVB-3 DVB-3 VENTILADOR...
  • Page 45 Gas Natural: CDV155D | Gas Propano: CDV156D ATTN: Contratistas y Técnicos de Servicio Calificados: Solo vendemos piezas a través de nuestros mayoristas. Para obtener un servicio de piezas rápido, comuníquese con el mayorista al que le compró su calentador Cozy. # RÉF.
  • Page 46 LISTA DE PIEZAS - DE HORNO DE PARED DIRECTA Gas Natural: CDV255D & CDV305D | Gas Propano: CDV256D & CDV306D = 17.145 cm Dia. = 10.6299 cm Dia. # Réf. 61, 62 y 63 No ilustrado EXTENSIONES OPCIONALES DEL RESPIRADERO VK1525 / 9-15 y VK30 / 9-15 Juego para el Ensamble de la Ventila VK15 / 25-15-24 Juego para el Ensamble de la Ventila...
  • Page 47 ATTN: Contratistas y Técnicos de Servicio Calificados: Solo vendemos piezas a través de nuestros mayoristas. Para obtener un servicio de piezas rápido, comuníquese con el mayorista al que le compró su calentador Cozy. Números de Modelo de Gas Natural ..
  • Page 48 VARIAR DE UN ESTADO A OTRO. duración de una garantía implícita, y algunos estados no permiten la exclusión o limitación de PARA REGISTRAR SU CALEFACTOR: Vaya en línea al sitio web de Cozy Heaters en: www.cozyheaters.com/warranty-registration/ COZY HEATING SYSTEMS, LLC 250 WEST LAUREL STREET –...
  • Page 49 Cet appareil est uniquement destiné à être utilisé avec le type de gaz indiqué sur la plaque signalétique. Cet appareil n’est pas convertible pour une utilisation avec d’autres gaz, sauf si un kit certifié est utilisé. Cozy Heating Systems, LLC | cozyheaters.com | 888-444-1212 | 250 West Laurel Street | Colton, CA 92324 Manuel Français...
  • Page 50 TABLE DES MATIÈRES LIRE ATTENTIVEMENT AVANT D’INSTALLER DE CETTE L’UNITÉ Ces directives d’installation servent de guide général et ne remplacent Avant L’Installation pas les codes locaux et ordonnances applicables. S’assurer de se Les Normes ........2 confonner à toutes les phases du code de chauffage local avant Spécifications ........
  • Page 51 SPÉCIFICATIONS - GÉNÉRATEUR INDIVIDUEL Votre chaudière murale à prise d’air directe est expédiée en un seul carton. Ce carton contient la chaudière, le capuchon d’aération, le tuyau d’aération, le tuyau d’ admission d’ air, le modèle des dimensions des robinetteries, les instructions d’installation et de fonctionnement et le câble du thermostat.
  • Page 52 SÉCURITÉ - A Continué nettoyage plus fréquent peut être requis s’ il y a un excès de 20. Si vous suspectez une montée d’eau dans la chaudière, coupez immédiatement le gaz. N’utilisez pas l’appareil si peluche provenant de tapis, literie, etc. Il faut absolument des pièces sont immergées.
  • Page 53 DÉGAGEMENTS TERMINAUX DE VENTILATION Coin F IX E Intérieur F E R M É B L E O P É R A Détail F IX É F E R M É = Borne De Passage = Admission D’Air = Secteur ou la Borne N’est Pas Autorisée INSTALLATIONS INSTALLATIONS...
  • Page 54 Min 30,48cm 1,27cm Plancher Plancher 10,16cm CDV15-D CDV25-D / CDV30-D Tous les Chapeaux D’évent EMPLACEMENT ET PRÉCAUTIONS SPÉCIALES EMPLACEMENT En raison des températures élevées, l’appareil de chauffage mural 1. L’appareil de chauffage mural doit être installé sur un mur extérieur.
  • Page 55 INSTALLATION ATTENTION: Si ces directives ne sont pas suivies prudemment, il pourrait y avoir comme conséquence un faible rendement, des dommages à la propriété, des blessures ou la mort. ÉTAPE 1 EMPLACEMENT DE L’OUVERTURE DU VENTILATION Déterminer l’emplacement des montants et centrer l’ouvexiure du ventilation de 22,9 mm (9 po) au moins 56 cm (22 po) au-dessus du sol pour un CDV15 et 61 cm (24-1/8 po) pour un CDV25/30.
  • Page 56 INSTALLATION DE LA FOURNAISE - MURS 22,86 CM FOURNAISE - MURS 38,10 CM À FOURNAISE- MURS 22,86 CM À À 38,10 CM (CDV15 / CDV25-D) 60,96 CM (CDV15/ CD V25-C) 38,10 CM (CDV30-D) Pour les murs de 22,86cm à 38.10cm, L’ensemble VK 1525115-24-B est destiné...
  • Page 57 INSTALLATION Schéma 4 CDV15-D CDV25/30-D 45,72 cm 87,63 cm Caisson Caisson Ouverture Ouverture dia. dia. 22,86 cm 22,86 cm Soupape 22,86 D’admission 71,76cm 33,97 42,23 de Gaz 80,65cm 55,88cm Soupape 61,28cm d’admission 20,32 de gaz 33,02cm Robinet 1.27cm Manométrique Plancer 10,16cm Robinet D’arrêt NPT .32cm...
  • Page 58 INSTALLATION Schéma 7 Poteau Mural Mur Intérieur Prolongation du Manchon D’emboîtement Mural Manchon D’emboîtement Mural Mur Extérieur Plaque-Entretoise du Tuyau de Ventilation Tuyau de Ventilation ALIMENTATION EN GAZ Schéma 8 Ce radiateur ventilé doit être raccordé à une alimentation en gaz capable de fournir une capacité...
  • Page 59 INSTRUCTIONS POUR L’ALLUMAGE MODÈLES: CDV155D / CDV156D / CDV255D / CDV256D / CDV305D / CDV306D PAR SOUCI DE SÉCURITÉ, LIRE AVANT D’ALLUMER MISE EN GARDE: Cet appareil est muni d’une veilleuse qui doit être gaz depuis un voisin. Suivez les instructions du SI VOUS NE allumée manuellment.
  • Page 60 ENTRETIEN MISE EN GARDE: Cet appareil fonctionne au gas. Ne pas entreposer ou utiliser de l’essence ou d’autres liquides ou vapeurs inflammables aux alentours de cet appareil. Toute matière combustible doit être gardée loin de cet appareil de chauffage afin d’éviter une incendie ou une explosion. Garder la foumaise et l‘aire de la fournaise propres pour un Ne pas obstruer l’air de combustion et de ventilation.
  • Page 61 ENTRETIEN ORIFICE DU BRÛLEUR Schéma 11: Altitudes Spécifiques La grosseur le l’orifice de cet appareil a été déterminée en Numéros 609.61 a 1219.21 a 1828.82 a 2438.43 a de Modéle 609.61m 1219.21 m 1828.82 m 2438.43 m 3048.04 m usine pour des altitudes jusqu’à 609,61 m. Si cet appareil est installé...
  • Page 62 ENTRETIEN Au moment de l’entretien des commandes étiquetez tous les fils avant le débranchement. ATTENTION: Des erreurs de câblage peuvent entraîner un fonctionnement inadéquat et dangereux. REMARQUE - La fournaise et tous ses composants doivent être inspectés au moins annuellement par un technicien d’entretien qualifié.
  • Page 63 TABLEAU DE DÉPANNAGE ( A utiliser par un installateur ou un technicien d’entretien qualifié. ) PROBLÈME CAUSE POSSIBLE ACTION CORRECTIVE FLAMME 1. Soupape defective. 1. Remplacer la soupape. TROP 2. Orifice trop grand du brûleur. 2. Vérifier avec la société gazière locale pour la taille appropriée d’orifice et remplacer. GRANDE 3.
  • Page 64 KIT SOUFFLEUR DVB-3 NOTICE D’INSTALLATION - ( FACULTATIF ) Ce kit doit être installé uniquement par un installateur qualifié ou un technicien de maintenance. Compatible avec les séries CDV15-D / CDV25-D / CDV30-D. ATTENTION: Au moment de l’entretien des commandes étiquetez tous les fils avant le débranchement.
  • Page 65 KIT SOUFFLEUR DVB-3 NOTICE D’INSTALLATION - ( FACULTATIF ) Ce kit doit être installé uniquement par un installateur qualifié ou un technicien de maintenance. Compatible avec les séries CDV15-D / CDV25-D / CDV30-D. Schéma 15-A SCHÉMA DESCRIPTION DE PIÈCE PIÈCE DÉCHELLE...
  • Page 66 INSTRUCTIONS D’INSTALLATION DU KIT BBSK - ( FACULTATIF ) Ce kit doit être installé uniquement par un installateur qualifié ou Schéma 16-A un technicien de maintenance. 2,06375cm CDV15 ÉTAPE 1. Trouvez l’emplacement de forage à l’arrière de l’armoire, près du sommet. Voir Schéma 16-A. 8,255cm ÉTAPE 2.
  • Page 67 INSTRUCTIONS D’ALLUMAGE DU MODÈLE BBSK - ( FACULTATIF ) PAR SOUCI DE SÉCURITÉ, LIRE AVANT D’ALLUMER MISE Cet appareil est équipé d’une veilleuse qui doit être instructions du fournisseur de gaz. EN GARDE: allumée manuellement. Il faut suivre scrupuleusement • S’il n’est pas possible d’atteindre le fournisseur Si vous ne ces consignes lors de l‘allumage de la veilleuse.
  • Page 68 APPARElL DE CHAUFFAGE MURAL À ÉVACUATION DIRECTE PAR VENTILATEUR - LISTE DES PIÈCES Gaz Natural: CDV155D | Gaz Propane: CDV156D = 17.145 cm Dia. = 10.6299 cm Dia. EXTENSIONS FACULTATIVES D’ÉVENT VK1525/9-15 Assemblage de L’ensemble de Ventilation VK1525/15-24 Assemblage de L’ensemble de Ventilation VENTILATEUR FACULTATIF / DVB-3 DVB-3 VENTILATEUR...
  • Page 69 Gaz Natural: CDV155D | Gaz Propane: CDV156D ATTN: Entrepreneurs et Techniciens de Service Qualifiés: Nous ne vendons des pièces que par l’intermédiaire de nos grossistes. Pour un service de pièces rapide, contactez le grossiste chez qui vous avez acheté votre appareil de chauffage Cozy. RÉF.
  • Page 70 APPARElL DE CHAUFFAGE MURAL À ÉVACUATION DIRECTE PAR VENTILATEUR - LISTE DES PIÈCES Gaz Natural: CDV255D & CDV305D | Gaz Propane: CDV256D & CDV306D = 17.145 cm Dia. = 10.6299 cm Dia. N o Réf. 61, 62 & 63 Non illustré. OPTIONAL VENT EXTENSIONS VK1525 / 9-15 et VK30 / 9-15 Assemblage de L’ensemble de Ventilation...
  • Page 71 ATTN: Entrepreneurs et techniciens de service qualifiés: Nous ne vendons des pièces que par l’intermédiaire de nos grossistes. Pour un service de pièces rapide, contactez le grossiste chez qui vous avez acheté votre appareil de chauffage Cozy. Numéros de Modèle Gaz Natural ..
  • Page 72 PEUT ETRE D’AUTRES DROITS VARIANT SELON RECOURS POSSIBLE POUR L’UTILISATEUR VOTRE PAYS POUR ENREGISTRER VOTRE FOURNAISE : Allez en ligne sur le site Web de Cozy Heaters à l’adresse : www.cozyheaters.com/warranty-registration/ COZY HEATING SYSTEMS, LLC 250 WEST LAUREL STREET – COLTON, CA 92324 Manuel Français...