Once the tester is powered on, it will automatically measure
voltage in the range of 6 V-690 V
When the L2 probe + is the positive (negative) potential, the
Polarity indication LED indicates '+DC' ('-DC')
In case of empty batteries: 50/120/230/400/690 V LEDs still
indicate the presence of voltage
7.4
Make sure the object under test isn't live.
•
Connect both test probes to the object under test
-
-
-
This test is only possible when batteries are installed and in good
condition
7.5
Function of this test may not be fully achieved if the insulation
condition/ grounding conditions of user or of the equipment
under test aren't good enough. Verification of live-circuit
shouldn't be dependent on this single-pole phase test only, but
on a 2-pole voltage test.
Firmly grasp the insulated grips of the main body of the tester in
order to increase the sensitivity of single-pole phase test.
Hold the tester good in your hand. Connect the '+' probe to the
object under test.
Live circuit LED lights up and buzzer sounds when a voltage of
approx. 100 VAC or more is detected on the object under test.
(Pol≥100 VAC).
Single pole indication is via LED
The single-pole phase test is only possible when batteries are
installed and in good condition
7.6
•
L LED (symbol) and R LED (symbol) for phase rotation test may
operate on various wiring systems, but effective testing result
can be obtained only on three-phase 4-wire system
•
Firmly grasp the insulated grip of the tester probe L2, it is better
for the sensitivity of the phase rotation test and connect both
probes to the object under test
•
Phase-to-phase voltage is indicated by voltage LEDs
•
R LED lights up for Right rotary field
L LED lights up for Left rotary field
•
Measurement principle: The instrument detects the phase
rising order regarding the user as earth.
•
Testing of phase-sequence direction is possible from 100 VAC
voltage (phase to phase) provided the neutral is earthed
•
Function of this test may not be fully achieved if the insulation
condition/ grounding conditions of user or of the equipment
under test is not good enough
7.7
•
Press the
will turn itself off
7.8
•
LEDs up to 50 V, torch light, ELV indication and buzzer are
turned on for a second after battery replacement or selftest
activation. Selftest can be activated:
Shorting L1(-) and L2(+) probe tips while device is turned
OFF – leave device OFF for 30 seconds before shortening tips
Continuity test
Continuity test is performed automatically
Buzzer/Continuity LED lights up and buzzer sounds
continuously to indicate continuity
Tester switch to voltage measurement if voltage is
detected during continuity testing >6 V
Single-pole phase test
Phase rotation test
Torch light
button to turn on the light and after approx. 30 s it
Self test
17