Please use H07RN-F for the power wire, all the cable are connect to high voltage except for thermistor cable and cable
for user interface.
Equipment must be grounded.
All high-voltage external load, if it is metal or a grounded port, must be grounded.
All external load current is needed less than 0.2A, if the single load current is greater than 0.2A, the load must be controlled
through AC contactor.
"AHS1" "AHS2" wiring terminal ports only provide the switch signal.
Expansion valve E-Heating tape,Plate heat exchanger E-Heating tape and Flow switch E-Heating tape share a control port.
Field wiring guidelines
Most field wiring on the unit is to be made on the terminal block inside the switch box. To gain access to the terminal block,
remove the handle sheet metal.
Switch off all power including the unit power supply and backup heater power supply (if applicable) before removing the
handle sheet metal.
Fix all cables using cable ties.
A dedicated power circuit is required for the backup heater.
Lay out the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover
securely.
Follow the electric wiring diagram for electrical wiring works (the electric wiring diagrams are located on the rear side of
handle sheet metal.
Install the wires and fix the cover firmly so that the cover may be fit in properly.
9.6.3 Precautions on wiring of power supply
Use a round crimp-style terminal for connection to the power supply terminal board. In case it cannot be used due to
unavoidable reasons, be sure to observe the following instructions.
-
Do not connect different gauge wires to the same power supply terminal. (Loose connections may cause overheating.)
-
When connecting wires of the same gauge, connect them according to the figure below.
Use the correct screwdriver to tighten the terminal screws. Small screwdrivers can damage the screw head and prevent
appropriate tightening.
Over-tightening the terminal screws can damage the screws.
Attach a ground fault circuit interrupter and fuse to the power supply line.
In wiring, make certain that prescribed wires are used, carry out complete connections, and fix the wires so that outside force
cannot affect the terminals.
9.6.4 Safety device requirement
1. Select the wire diameters( minimum valve) individually for each unit based on the table 9-1 and table 9-2, where the rated
current in table 9-1 means MCA in table 9-2. In case the MCA exceeds 63A, the wire diameters should be selected according
to the national wiring regulation.
2. Maximum allowable voltage range variation between phases is 2%.
3. Select circuit breaker that having a contact separation in all poles not less than 3 mm providing full disconnection,where MFA
is used to select the current circuit breakers and residual current operation breakers.
NOTE
WARNING