Screw hole installed on the
three M4X20
Screw hole installed on 86
Electrician box, use two
M4X25
1 ) Use straight head screwdriver to insert in the buckling position in
the bottom of wired controller, and spin the screwdriver to take down
the back cover. (Pay attention to spinning direction, otherwise will
damage the back cover!)
2) Use three M4X20 screws to directly install the back cover on the
wall.
3) Use two M4X25 screws to install the back cover on the 86
electrician box, and use one M4X20 screws for fixing on the wall.
4) Adjust the length of two plastic screw bars in the accessory to be
standard length from the electrical box screw bar to the wall. Make
sure while installing the screw bar to the wall, making it as flat as the
wall.
5) Use cross head screws to fix the wired controller bottom cover in
the wall through the screw bar. Make sure the wired controller bottom
cover is on the same level after installation, and then install the wired
controller back to the bottom cover.
6) Over fastening the screw will lead to deforma tion of back cover.
A
Cutting place of left
down side wire outlet
B
Wiring
60mm
hole
Back cover
Signal
switching
wires
Left down
side wire
outlet
C
Wall hole and wiring hole
Diameter: Φ8--Φ10
Putty
Trap
Avoid the water enter into the wired remote controller, use trap
and putty to seal the connectors of wires during wiring
installation.
10.4.4 Front cover installation
After adjusting the front cover and then buckle the front cover;
avoid clamping the communication switching wire during
installation.
Correct install the back cover and firmly buckle the front cover and
back cover, otherwise will make the front cover drop off.
10.5 Field settings
The unit should be configured to match the installation
environment (outdoor climate, installed options, etc.) and user
demand. A number of field settings are available. These
settings are accessible and programmable through "FOR
SERVICEMAN" in user interface.
Powering on the unit
When the unit is powered on, "1%~99%" is displayed on the
user interface. During this process the user interface cannot
be operated.
Procedure
To change one or more field settings, please refer to "FOR
SERVICEMAN" for details
Temperature values displayed on the wired controller
(user interface) are in °C.
38
Putty
Putty
Trap
Trap
Sensor can not be
affected with damp.
NOTE