8.
Vent Pipe Installation
[ For N-0751M]
CARBON MONOXIDE POISONING
Follow all vent system requirements in accordance with relevant local or state regulation,
or, in the absence of local or state code, in the U.S. to the National Fuel Gas Code ANSI
Be sure to do
Z233.1/NFPA 54 – latest edition, and in Canada, in accordance with NSCNGPI.
Vent Piping
• Use only UL listed category III vent materials.
• Follow the vent pipe manufacturer's installation
instructions.
Pipe diameter
No. of Elbows
3
2
1
• Make the vertical section of the exhaust vent
as short as possible.
• Maintain the same vent pipe diameter from the
heater flue to the vent termination.
Clearances
Manufacturer and
Product
Noritz N-Vent
Protech FasNSeal
Protech FasNSeal W2
HeatFab SafTVent
Z-Flex Z-Vent
Flex-L-StaR-34
These clearances are subject to change.
Refer to the UL listing for the proper clearances.
All manuals and user guides at all-guides.com
WARNING
100mm (4")
Max. Straight Vent Length
4.6m (15')
8.2m (27')
11.7m (39')
Enclosed
Unenclosed
Hor.
Vert. Hor. Vert.
250mm (10") (sides)
100mm
75mm
75mm
375mm (15") (top)
(4")
(3")
150mm (6") (bottom)
100mm
75mm
200mm (8") (sides)
75mm
300mm (12") (top)
(4")
(3")
100mm (4") (bottom)
150mm
100mm
75mm
75mm
(6")
(4")
(3")
150mm
50mm
50mm
150mm
(6")
(6")
(2")
200mm
100mm
25mm
25mm
(8")
(4")
(1")
200mm
100mm
25mm
25mm
(8")
(4")
(1")
(Indoor Installation Only)
• The first vertical run from the top of the heater
should be no longer than 0.9m (3').
• Make sure vent pipe is gas tight and will not
leak. Use silicon sealant wherever necessary.
• Do not common vent or connect more than
one appliance to this venting system.
• The total vent length including horizontal & verti-
cal vent runs should be no less than 0.9m (3').
• Do not place any dangerous objects at the end
of the exhaust vent and check that vent pipe is
not blocked in any way.
• Steam (smoke) or water drops may come out
from the end of the exhaust pipe. Select the
location for the end of the vent so that steam is
not visible, and the vent is not wet with drip-
ping water.
• If snow is expected to accumulate, take care
the end of the pipe is not covered with snow or
hit by falling lumps of snow.
• Consult the vent pipe manufacturer's install-
ation instructions for chimney connections.
(3")
Appliance Adapters
• Use the following adapters to connect the
(3")
unit to the venting system.
(3")
Manufacturer and
(2")
Product
(1")
Protech FasNSeal
(1")
HeatFab SafTVent
Z-Flex Z-Vent
Flex-L Star-34
Part No.
FSAA4
9401RYPK
2SVWA04
SRASPSA4
13