Télécharger Imprimer la page

Southwire X-TREME BOX 706UGCX Mode D'emploi page 3

Publicité

Les langues disponibles

Les langues disponibles

1. Panel mount GFCI PN# GF6095 or 18900000
2. 20A 125V twist-to-lock receptacle PN# 205R or 18910000
3. 20A 125V straight-blade receptacle PN# 520R1 or 18920000
4. 50A 125/250V receptacle, "CS" PN# 6369H or 18940000
5. 50A 125/250V flanged inlet, "CS", PN# 6375H or 18960000
6. 20A single pole circuit breaker PN# CB120NS or 18970000
7. 30A double pole circuit breaker PN# CB230NS or 18980000
8. Cover for 20A and 30A TL receptacles PN# 7420 & GAS7420
9. Cover for 20A straight blade receptacles, PN# 7421 & GAS7421
10. Sled Legs (pair) PN# 350-00064
11. Housing top cover, yellow PN# 350-00186
12. 50A 125/250V Receptacle Cover, PN# 7788 & GAS7788
13. 50A 125/250V Inlet Cover, PN# 7780 & GAS7780
14. Circuit Breaker Interior, PN# INT
15. Neutral Bus Bar, PN# 10NEU125B
16. Grounding Bus Bar, PN# GBK10
17. 30A 250V Twist-to-Lock receptacle, PN# 306R
SERVICE AND REPAIR ARE TO BE PERFORMED BY QUALIFIED PERSONNEL
ONLY.
CORD SETS AND RELATED PRODUCTS
19370008/6425S
25' 6/3 & 8/1 SEOW 125/250V 50A cord set, Hubbell "L"fittings
1918008/6450S
50' 6/3 & 8/1 SEOW 125/250V 50A cord set, Hubbell "L" fittings
1938008
50' 6/3 & 8/1 SEOW 125/250V 50A cord set, Hubbell "C" fittings
1919008/6400S
100' 6/3 & 8/1 SEOW 125/250V 50A cord set, Hubbell "L" fittings
19390008
100' 6/3 & 8/1 SEOW 125/250V 50A cord set, Hubbell "C" fittings
19200008/6404M
6/4 SEOOW 125/250V 50A "Y" adapter
18240008
10' 10/4 dryer adapter cord, 14-30P to Hubbell "L" connector
18340008
10' 6/3 & 8/1 range adapter cord, 14-50P to Hubbell "L"
connector
1-855-SWTOOLS — www.southwiretools.com
Southwire Company offers a full line of cord sets, adapters, and user-at-
tachable fittings for construction site applications.
THEORY OF OPERATION
The X-TREME BOX™ portable power distribution center is intended for
connection to a split-phase 125/250V 50A power source. This source may
be a generator or a utility power drop. The input connection is through a
"California Standard" 3-pole 4-wire grounding twist-to-lock power inlet.
The power inlet feeds into a split-phase circuit breaker panel with (6) 1-pole
20A breakers and (1) 2-pole 30A breaker.
Each 20A circuit breaker powers a Class "A" ground fault circuit interrupter
(GFCI), which in turn powers a 2-pole 3-wire grounding 20A receptacle,
either straight-blade or twist-to-lock, depending on the catalog number. The
30A 2-pole circuit breaker powers a 3-pole 4-wire grounding 125/250V 30A
twist-to lock receptacle. The 30A receptacle does not provide ground fault
protection.
Each GFCI has a high-voltage detection circuit. If the voltage rises too high,
which can result from wiring problems such as an open neutral, the GFCI
will turn off. This helps to prevent damage to tools and equipment plugged
into the receptacle. An indicator lamp is provided on the GFCI to alert the
operator to the over-voltage condition.
TROUBLESHOOTING TIPS
The status of each 20A receptacle is indicated on its associated GFCI. The
power indicator lamp, between the TEST and RESET buttons, is illuminated
if power is available at the receptacle. If a lamp is not illuminated, and the
circuit breaker is "ON", check the wiring to the unit:
If the power indicator lights on (3) GFCIs are off, one side of the split-phase
input (one of the "Hot" lines) may be missing.
If the power indicator lamps on (3) of the GFCIs are off, and the "High
Voltage" lamps on the other (3) GFCIs illuminate, the neutral line may be
missing. An open neutral may not be evident until a load is applied to one of
the receptacles.
1-855-SWTOOLS — www.southwiretools.com

Publicité

loading

Ce manuel est également adapté pour:

X-treme box 8706tlcxX-treme box 6506ugsxX-treme box 6506tlsx