in the control system affects the correct cooling and thus the operation and
lifespan of the inverter.
Temperature protection
If the cooling provided by the fan is insufficient, the temperature protection will be
activated. The inverter will shut down the 230VAC output and the red 'fault'
indicator will light. Once the inverter has cooled down sufficiently, it will restart
automatically.
Pre-warning (buzzer)
If the input voltage is becoming low, the inverter will emit an acoustically pulsed
signal as a warning.
12Volt models
24Volt models
With the PLUS models, the pre-warning value can be adjusted via the PurePower
app. The acoustic signal can also be switched off.
Low voltage protection.
If, after the pre-warning, the input voltage still drops further, the low voltage
protection will eventually take effect. The 230VAC output is shut down and the red
indicator 'fault' will light. The acoustic signal will sound uninterruptedly. If the input
voltage has risen again sufficiently, the inverter will automatically restart.
12Volt models
24Volt models
With the PLUS models, these values can be adjusted via the PurePower app. The
acoustic signal can also be switched off.
Over voltage protection
If the input voltage rises too high, the overvoltage protection will come into effect.
The 230VAC output is shut down and the red 'fault' LED lights up. The acoustic
signal will sound uninterruptedly. If the input voltage has dropped sufficiently, the
inverter will automatically restart.
12Volt models
24Volt models
With the PLUS models, the shut down value can be adjusted via the PurePower
app. The acoustic signal can also be switched off.
13
Activation
+/- 10,5Vdc
+/- 21,0Vdc
Shut down
+/- 10,0Vdc
+/- 20,0Vdc
Shut down
+/- 16,5Vdc
+/- 33,0Vdc
De-activation
+/- 11,5Vdc
+/- 23,0Vdc
Auto-restart
+/- 12,6Vdc
+/- 25,2Vdc
Auto-restart
+/- 14,5Vdc
+/- 29,0Vdc