30 AMP CIRCUIT- LOCK™ DISCONNECT SWITCH WITH LED INDICATORS
GENERAL INFORMATION
CAUTION: Disconnect Power Before Servicing.
WARNING:
For use with three-phase Y configuration only. Do not use with delta configuration.
HBLDS3P LED indicators (See Figure A). Perform wiring instructions per PD1782. Provided.*
HBLDS3SSP LED indicators (See Figure B). Perform wiring instructions per PD2520. Provided.*
HBLDS3SSRP LED indicators (See Figure C). Perform wiring instructions per PD2665.Provided.*
CIRCUIT BOARD WIRING INSTRUCTIONS:
1. See figures A, B, or C. WARNING: Accidental dropping or rough handling of cover during installation can cause damage.
To aid installation place cover as shown. (See Figures A, B, or C).
2. Loosen terminal screws and secure (6) black wires with male tabs marked L1, L2, L3, T1, T2, T3 to corresponding terminations
on switch. Tighten terminal screws to 18 pound-inches (2.0 N-m). Secure green ground wire from circuit board to thinner (width)
ground buss. Tighten grounding buss terminal screw to 7.1 pound-inches (.800 N-m).
3. Install cover. The handle must be in the OFF position. Tighten the four (4) cover screws to 18 pound-inches (2.0 N-m) for
HBLDS3P, and 24 pound-inches (2.7 N-m) for HBLDS3SSP and HBLDS3SSRP.
CAUTION:
When completed with wiring fully
remove support screw and remove
cover for re-installation. DO NOT
ROTATE into position. Rotating into
position can result in damage to the
circuit board assembly underneath
the cover.
For top feed or bottom feed conduit
application it is recommended to
screw in bottom screw a few
threads to hold cover temporarily
while installing circuit board wires or
servicing switch.
CAUTION:
When completed with
wiring fully remove
support screw and
remove cover for re-
installation. DO NOT
ROTATE into
position. Rotating into
position can result in
damage to the circuit
board assembly
underneath the cover.
For top or bottom
feed application it is
recommended to
screw in bottom
screw a few threads
to hold cover
temporarily while
installing circuit
board wires or
servicing switch.
Wiring Device-Kellems
Hubbell Incorporated (Delaware)
1-800-288-6000
Shelton, CT 06484
www.hubbell-wiring.com
PD2790 (Page 1)
02/17
FOR HBLDS3P, HBLDS3SSP, AND HBLDS3SSRP
* Complete assembly steps up to cover installation.
Figure A
If a bottom feed
conduit application
is desired you may
place cover on top
of enclosure
temporarily while
installing circuit
board wires or
servicing switch.
Figure B
If a bottom feed conduit application is
desired you may place cover on top of
enclosure temporarily while installing circuit
board wires or servicing switch.
CAUTION:
When completed with
wiring fully remove
support screw and
remove cover for re-
installation. DO NOT
ROTATE into
position. Rotating into
position can result in
damage to the circuit
board assembly
underneath the cover.
Screw in bottom screw a
few threads to hold cover
temporarily while installing
circuit board wires or
servicing switch.
Figure C

Publicité

loading

Sommaire des Matières pour Hubbell HBLDS3P

  • Page 1 WARNING: For use with three-phase Y configuration only. Do not use with delta configuration. HBLDS3P LED indicators (See Figure A). Perform wiring instructions per PD1782. Provided.* HBLDS3SSP LED indicators (See Figure B). Perform wiring instructions per PD2520. Provided.* HBLDS3SSRP LED indicators (See Figure C). Perform wiring instructions per PD2665.Provided.* * Complete assembly steps up to cover installation.
  • Page 2 HUBBELL 30 AMP CIRCUIT-LOCK ™ & MOTOR QUICK ® DISCONNECT SWITCH English This enclosure provides ON-OFF switched control of a directly connected load and meets the requirements of Outdoor/Indoor (Type 4X, Watertight, Corrosion Resistant), Indoor (Type 12 Dust Tight) and Outdoor/Indoor (IP69k, High Pressure, High Temperature & Dust) installations.
  • Page 3 7. Select the correct wiring diagram. Loosen terminal screws. Insert conductors fully into proper terminals. 8.Tighten terminal screws as follows: SWITCH terminals: 12‑15 lb•in (1.4‑1.7 N•m); gROuND and NEuTRAL terminals 14.2 lb•in (1,6 N•m). 1 Enclosure 9.Tighten the grounding buss mounting screw to 4.4‑8.9 lb•in (0.5‑1.0 N•m). 2 Mounting foot 10.
  • Page 4 SECTIONNEUR CIRCUIT-LOCK INTERRUPTOR CIRCUIT-LOCK MOTORQUICK DE HUBBELL • 30 A MOTORQUICK DE HUBBELL • 30 A Español Français Ce boîtier permet la commutation ON-OFF d’une charge raccordée directement et satisfait Esta envolvente proporciona control de ENCENDIDO-APAGADO de una carga directamente conectada y cumple con los requerimientos para las instalaciones al exterior/interior (Tipo 4X, hermético,...
  • Page 5 HUBBELL DE MEXICO garantiza este producto, de estar libre de defectos en materiales y mano de obra por un año a partir de su compra. HUBBELL reparará o reemplazará el articulo a su juicio en un plazo de 60 días. Esta garantía no cubre desgastes por uso normal o daños ocasionados por accidente, mal uso, abuso o...

Ce manuel est également adapté pour:

Hblds3sspHblds3ssrp