5.- Warnings
Detectors measure gas concentration in a point, if the gas leak does not reach the detector, the alarm will
Ÿ
not activate.
Detectors cannot supervise areas, and if perimeter supervision is required, several detectors should be
Ÿ
installed surrounding the area to be supervised.
Thoroughly studying the location of the detector/s is recommended, bearing in mind the areas most sensitive to
Ÿ
suffering leaks, the type of gas used, the size and shape of the room, the air flows, the maintenance work, etc.
The detectors described have been designed to detect gas concentrations capable of affecting the
Ÿ
environmental conditions of the room (movement of oxygen), and the detection of small coolant leaks is not
guaranteed.
6.- Operation
Alarm station
ESTADO
With power supply
Without power
supply/With battery
Without power
supply/Without battery
* Input indicators with connected gas detectors will stay on indicating that they are disabled. The rest of the inputs
will turn on in the event of an alarm (active button).
Luminous button
CENTRAL
BUTTON
Detector/wiring
fault
1
The input indicator corresponding to the active button will turn on.
1
2
3
4
3
4
According to
ON
active alarms
Flashing
ON*
OFF
OFF
1
2
3
Off
Off
1
On
On
1
On
On
ALARM STATION
RELAYS
Gas Alarm
Trapped person
According to
According to
active alarms
active alarms
According to
active alarms
1
2
3
4
1
2
3
4
ALARM STATION
ACOUSTIC
TRAPPED PERSON
4
ALARM
Off
Two-tone sound
3 short tones every
2 minutes
22
OBSERVATIONS
-
Disabled gas
detectors
-
5
6
7
ALARM RELAY
5
6
7
5
6
7
5
6
7