High humidity and low temperatures inside the enclosure can lead to condensation on the evaporator.
Condensate that flows back into the enclosure can damage sensitive control electronics.
If too much condensation forms, the condensation is drained out of the cooling unit from outlets in the front
bottom cover (Position 1, 3 and 4) or directly through the bottom of the unit (Position 2). The drain pipe must be
connected wherever is most suitable for the customer application.
To install the drain pipe directly through the bottom of the unit (Position 2) please follow below steps:
1.
Remove the top cover, middle cover, and bottom cover. The top cover does not need to be removed on
the RK-7525 and RK-7555. The louver blanks that are marked with an arrow need to be removed carefully
with a flat blade screwdriver. Then a torx screwdriver is to be used to loosen the screws behind the
removed louver blanks. There is no need to completely remove the screws.