For 5 kV maximum: Thoroughly scrape all wax
and dirt 5" back from each cable end. Prepare cable
ends exactly as shown. Do not cut insulation while
removing outer sheath. See Table A for proper sizing
and dimensions.
Bare Conductor ................................A
Insulation Pencil ..............................B
Maximum Sheath Opening ..............L
4.0 Installation
4.1
Install End Caps. Trim conical ends of end caps at
proper guide marks to provide a firm sliding fit on cable
sheath. Slip end caps onto each cable.
4.2
Install Mold Body. Slip mold body onto one cable end.
5.0 Connection
5.1
Join conductors with compression-type connectors.
Follow connector manufacturer's instructions.
5.2
Multi-conductor Cables. Stagger individual connectors
(provide lateral spacing of 1/2" between ends of
connectors) and insulate connector with Scotch™ 23
Electrical Tape. For 600 volts or less, use 3M™
Scotchlok™ Insulated Butt Connectors.
Note: Connectors not provided with kit.
B
B
A
A
L
5 kV maximum