8. FONCTIONS D'AFFICHAGE
8.2
INTERVENTION DES ALARMES
on
SI LE CORRECT FONCTIONNEMENTL DE LA BATTERIE (INVERSIONE,
SULFATATION, INTERRUPTION) EST COMPROMIS:
• L'ALARME D'ANORMALIE BATTERIE S'ACTIVERA,
• LE VOYANT JAUNE CORRESPONDANT S'ALLUMERA
• L'ALERTE GENERALE DE SORTIE S'ACTIVERA
• LA SORTIE ALIMENTEE PAR LA SIRENE EXTERIEURE S'ACTIVERA
• LE MESSAGE SMS SERA ENVOYE:
'AVERTISSEMENT ANORMALIE/MAINTENANCE DU SYSTEME'
L'ALARME SE REINITIALISERA DES QUE L'ANORMALIE SERA RESOLUE
POUR GARANTIR LA CONTINUITE DU SERVICE MEME EN L'ABSENCE
D'ALIMENTATION ELECTRIQUE (URGENCE) VERIFIER IMMEDIATEMENT
L'ETAT DE CHARGE DES BATTERIES ET LEUR CORRECTE CONNEXION
SI EN MANQUE D'ALIMENTATION ELECTRIQUE (URGENCE), LA TENSION
DES BATTERIES DU SYSTEME DESCEND SOUS LE NIVEAU D'ALARME:
• L'ALARME BATTERIE DECHARGEE S'ACTIVERA,
• LE VOYANT ROUGE CORRESPONDANT S'ALLUMERA
• LE BUZZER (SI ACTIF) SONNERA
• L'ALERTE DE SORTIE GENERALE S'ACTIVERA
• LA SORTIE ALIMENTEE PAR LA SIRENE EXTERIEURE S'ACTIVERA
• LE MESSAGE SMS SERA ENVOYE:
'AVERTISSEMENT ANORMALIE/MAINTENANCE DU SYSTEME'
L'ALARME SE REINITIALISERA ET LA CHARGE SE RETABLIRA DES QUE
LA TENSION DE LA BATTERIE RETOURNERA A UNE VALEUR NORMALE.
L'APPAREIL REUSSI A RECHARGER LES BATTERIES SEULEMENT AVEC LA
TENSION D'ALIMENTATION INSEREE DONC IL EST CONSEILLE DE
L'ETEINDRE JUSQU'A CE QU'IL SOIT RESTAURE
SI LE COURANT DU DEMARRAGE DE LA CHARGE EST PLUS ELEVE QUE
CELUI CONSENTI PAR LE SYSTEME:
• LE DEMARRAGE DE LA PROTECTION DE SURRINTENSITE S'ACTIVERA,
• LE VOYANT BLEU "ON" CLIGNOTERA
LA PROTECTION NE PEUT ETRE REINITIALISER ET LA CHARGE EST DONC
INAPTE
LE SYSTEME REPETERA 5 DEMARRAGES AVANT DE SIGNALER L'ALARME
D'ANORMALIE DE CHARGE (VOIR PG. 36)
POUR EVITER DE REDUIR LA VIE ET L'EFFICACITE DES BATTERIES IL
EST CONSEILLE D'ETEINDRE LE SYSTEME ET DEBRANCHER LE CHARGEUR