3.2
Electrical connection
Important :
personnel. Check that the cable supplying the technical room has a sufficiently large cross-section
to support the additional consumption required by the machine.
The heat pump must be supplied from an independent D-curve circuit breaker which can be either on
the main electrical panel equipped with a differential or on an independent panel connected to the main panel,
which will have a differential. If this is not the case, add a differential to the independent panel of your heat pump.
Référence
WPoséidon
80
WPoséidon
175
Electrical connection on the terminal block of the heat pump
Unscrew the handle to access the electrical connection
The connection of your heat pump must be carried out by authorised and qualified
D-Curve circuit
Power Supply
breaker power
Triphasé 380 V
40 Ampères
Triphasé 380 V
80 Ampères
Cable section according to the distance
between the circuit breaker and the heat pump
- 10 m
10 -15 m
3G6 mm2
3G10 mm2
3G16 mm2
3G25mm2
Three-phase
L :
Line
N :
Neutral
:
Earth
+ 15 m
3G10 mm2
3G25 mm2