11.1 Set hysteresis RH
Select "Humidity +/-" and the select the allowed
deviation.
Press the PTK to confirm.
Humidity day 60%
Hum. night
60%
=> Humidity +/-
3%
>> NEXT >>
11.2 Minimum/maximum RH level
Select >> NEXT >>.
Humidity day 60%
Hum. night
60%
Humidity +/-
3%
=> >> NEXT >>
Now you can read the minimum/maximum humidity
level.
To reset, select "Reset min/max" and press the PTK.
RH Min
49%
RH Max
54%
=> Reset min/max
>> NEXT >>
Select >> NEXT >> and press the PTK to return to the
main menu.
RH Min
49%
RH Max
54%
Reset min/max
=> >> NEXT >>
12. Measurement CO
The Clima Control Plus displays the current CO
and the measured minimum/maximum CO
2 or S-4 Sensor is connected. However, the Clima
Control Plus does not control the CO
____________________________________________________________________________________________________________________________
TechGrow
| Innovative Growing Solutions
All manuals and user guides at all-guides.com
level
2
level
2
levels, if a S-
2
level.
2
TMP = 33.6 °C
RH =
66%
BOX =
90%
=> CO2 = 1112 PPM
The main screen displays the current CO
access the next screen, select "CO2" and press the PTK.
CO2 Min
643PPM
CO2 Max
760PPM
=> Reset min/max
>> NEXT >>
Now you can read the minimum/maximum CO
To reset, select "Reset min/max" and press the PTK.
Select >> NEXT >> and press the PTK to return to the
main menu.
CO2 Min
643PPM
CO2 Max
760PPM
=> Reset min/max
>> NEXT >>
13. Connect the alarm contact
The Clima Control Plus is equipped with a change-over
contact for the alarm output, suitable for 230V at 1A.
Therefore, this contact is not suitable for high capacities,
but is intended to control an external relay.
If the Clima Control Plus is switched off or if all values
are correct, the NC contact will be connected to the
common (COM) connection; the NO contact is not
connected to anything in this state.
If the temperature rises too high, the change-over
contact will switch, so that the NO contact will be
connected to the common (COM) connection; the NC
contact is not connected to anything in this state.
Go through the following steps for a proper connection:
1. Unscrew the front plate (the small one with the
sockets) and lift it off the housing.
2. Put the alarm cable through the right swivel.
3. Connect the wires of the alarm cable to the right
terminal block, by pressing down the tiny white lever
with a small screwdriver and inserting the cable into
the corresponding hole.
level. To
2
levels.
2
22