OUTPUT:
The output is adjustable from front potentiometer in the range 5...24 VDC. A
green LED indicates active output. Short-circuit protection limits the current to
typ. 2.2 Amp. Output is isolated by 3.75 kVAC from input.
ELECTRICAL SPECIFICATIONS:
Specifications range:
(@-20°C to +60°C)
Common specifications:
Internal consumption max. ........................ 4 W
Isolation test / operation............................. 3.75 kVAC / 250 VAC
Transformer................................................. EN 60 742
Temperature coefficient .............................. 0.05% / °C
Mains effect (±10%).................................... < ±30 mV
Transient stability (10%-max. load) ............ < 250 mV
EMC immunity influence............................. < ±0.5%
Relative air humidity ................................... < 95% RH (non-cond.)
Dimensions (HxWxD) .................................. 80.5 x 35.5 x 84.5 mm
Tightness .................................................... IP50
Weight ......................................................... 425 g
Input:
Input voltage ............................................... 24 VAC ±10%
Frequency ................................................... 50...60 Hz
Output:
Output voltage ............................................ 5...24 VDC ±5%
Output power.............................................. Max. 7 W
Output current ............................................ 1 A / 5 VDC
Load effect, (10%-max. load) ..................... < 1.5% / A
18
All manuals and user guides at all-guides.com
110 VAC ±10%
120 VAC ±10%
230 VAC ±10%
0.55 A / 12 VDC
0.45 A / 15 VDC
0.3 A / 24 VDC
Current limit (short circuit) .......................... Typ. 2.2 A
Output ripple............................................... < 20 mVRMS
Observed authority requirements:
EMC 89/336/EEC, Emission....................... EN 50 081-1, EN 50 081-2
Immunity....................... EN 50 082-2, EN 50 082-1
Emission and immunity ......................... EN 61 326
LVD 73/23/EEC ........................................... EN 61 010-1
PELV/SELV .................................................. IEC 364-4-41 and EN 60 742
Standard:
19