Supported Function Code
Function code
01 (01h)
02 (02h)
03 (03h)
05 (05h)
15 (0Fh)
Function code:
Type:
Address
00001
00002
00003
00004
00005
00006
00007
00008
00009
00010
00011
00012
00013
00014
00015
00016
Function code:
Type:
Address
10017
10018
10019
10020
10021
10022
10023
10024
10025
10026
10027
10028
10029
10030
10031
Document no. G1002r19fr
Name
Read Coils
Read Discrete Inputs
Read Holding Register
Write Single Coil
Write Multiple Coil
0x01, 0x05, 0x0F
R/W, Bit access
Reg
Name
Reserved
0x00
0x01
Reserved
0x02
Reserved
0x03
Reserved
0x04
Reserved
0x05
Reserved
0x06
Reserved
0x07
Reserved
0x08
Scan speed
0x09
Calibration type
0x0A
Unit
0x0B
Reserved
0x0C
wtune
Reserved
0x0D
0x0E
Reserved
0x0F
Reserved
0x02
Read only, Bit access
Reg
Name
0x10
Channel 1 status
0x11
Channel 2 status
0x12
Channel 3 status
0x13
Channel 4 status
0x14
Channel 5 status
0x15
Channel 6 status
0x16
Channel 7 status
0x17
Channel 8 status
0x18
Channel 9 status
0x19
Channel 10 status
0x1A
Channel 11 status
0x1B
Channel 12 status
0x1C
Channel 13 status
0x1D
Channel 14 status
0x1E
Channel 15 status
Tous droits réservés. Neoptix Canada LP
Usage
Read device config
Optical signal present
Read temperatures
Write device config
Write device config
0 meaning
1 meaning
valid
invalid
valid
invalid
valid
invalid
valid
invalid
valid
invalid
valid
invalid
valid
invalid
valid
invalid
Slow
Fast
Neoptix
Nortech
C
F
valid
invalid
disable
enable (optimize CCD time)
valid
invalid
valid
invalid
valid
invalid
0 meaning
1 meaning
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected
No signal *
Probe detected