Télécharger Imprimer la page

Arcotherm GP 25 A Livret D'entretien page 15

Publicité

Les langues disponibles

Les langues disponibles

OBSERVED FAULTS, CAUSES AND REMEDIES
Air heater does not start
Air heater stops burning and lamp (1) lights up
Fan turns but the gas supply is blocked or fails to ignite
The flame extinguishes completely after the press-button is released
Gas supply is interrupted. The flame extinguishes
Too much gas is used
Air heater cannot be switched off by means of the switch
1
No electrical supply
2
Motor is overloaded (fan blows irregularly or is blocked)
3
Thermostat or time-clock setting incorrect
4
Thermostat plug (2) not shorted
Switch defect:
5
(4) on model "A" and (6) on model "M"
6
Fault in the burner relay
7
No gas pressure up to solenoid valves
8
Solenoid valves do not open
Ionisation electrode defective and/or ignition electrode wrongly
9
adjusted
10
Gauze protecting fan is dirty
11
Overheat thermostat cuts in
12
Thermostat out of order
13
Thermic gas valve does not remain open
14
Ignition does not work
15
Thermocouple does not get warm
16
Circuit breaker on thermocouple defective
17
Pressure regulator defect
18
Gas leakage
19
Solenoid valves do not close
20
Not enough airflow
21
Fault in air microswitch
All manuals and user guides at all-guides.com
OBSERVED FAULTS
REMEDY
Cause
15
Model "A"
1-2-3-4-5-6
6-7-8-9-10-20-21
9-10-11-17
17-18
5-6-12-19
Solution
Check that the plug is in socket and supply available
Check motor and fan and replace if necessary
Adjust setting
Make the connection (check the link connection in the plug)
Shut off the gas supply, remove plug from socket and replace switch
Replace the burner relay
Check that the gas supply is open
Check that the gas bottle(s) is (are) filled. Press the button of the
safety cut off valve
Check solenoid valves
Check the electrical connection
Check the overheat thermostat
Adhiust according to the instructions
Replace ionisation electrode
Clean the protection gauze
Check if the grilles at the inlet and outlet are dirty
Check that there is sufficient fresh air supply
Check that the heated air can flow out freely
Check the thermostat and replace, if necessary
Depress the valve button for about 10 seconds
Check line continuity between igniter and electrode
Check the setting of the electrode (see scheme)
Check the position of the thermocouple (see scheme)
Check the thermocouple and replace if necessary
Clean terminals of circuit breaker or replace
Replace pressure regulator
Locate the leak with soap-suds and replace the defective part
Close the gas supply, allow the available gas in the hose to burn, remove
plug from the socket, remove solenoid valves, clean and remount
Check if the grilles at the inlet and outlet are dirty
Check air microswitch
GB
CAUSE
Model "M"
1-2-5
7-10-11-12-13-14
13-15-16
17-18
5-19

Publicité

loading

Ce manuel est également adapté pour:

Gp 45 aGp 90 a