3.2.2
APERÇU DES FONCTIONS DU NIVEAU SETUP
FONCTIONS ET VARIABLES DU NIVEAU SETUP
1
TOTAL
11
UNIT
12
DECIMALS
13
K-FACTOR:
14
DECIMALS K-FACTOR
2
FLOWRATE
21
UNIT
22
DECIMALS
23
K-FACTOR
24
DECIMALS K-FACTOR
25
CALCULATION
26
CUT-OFF
27
DAMPING
3
ALARM
31
ALARM SET
32
FLOW ZERO
33
ALARM LO
34
ALARM HI
35
DELAY LO
36
DELAY HI
37
REL OUT
4
DISPLAY
41
FUNCTION
42
LCD NEW
43
BACKLIGHT
44
BACKLIGHT ALARM
45
BL. BRIGHTNESS
46
BATTERY MODE
5
FLOWMETER
51
SIGNAL
3
L - m
- kg - lb - GAL - USGAL - bbl - no unit
0 - 1 - 2 - 3 (Ref: displayed value)
0.000010 - 9,999,999
0 - 6
l/min – l/hr – m
g/min - g/hr – kg/sec – kg/min – kg/hr – kg/day – ton/min
– ton/hr – ton/day – gal/sec – gal/min – gal/hr – gal/day –
bbl/sec – bbl/min – bbl/hr – bbl/day – lb/sec – lb/min –
lb/hr – lb/day – cf/sec – cf/min – cf/hr – rev/sec – rev/min
– none – l/sec
0 - 1 - 2 - 3 (Ref: displayed value)
0,000010 - 9 999 999
0 - 6
per 1 - 255 pulses
0.1 - 999.9 seconds
0.1 - 999.9 seconds
Operate – Setup -- Hide
Default – No Relay – Ignore
-999,999 .. 999 999
-999,999 .. 999 999
0..999.9 sec
0..999.9 sec
Lo – Hi – Lo+Hi – Pulse – Off
total - flowrate
fast - 1 sec - 3 sec - 15 sec - 30 sec - off
off - green - amber
Off – on – flash
1 - 5
operational - shelf
npn - npn_lp - reed - reed_lp - pnp - pnp_lp - namur -
coil_hi - coil_lo - active
FW-F018-P-M_v0101_21_FR.docx
/sec – m
/min – m
/hr – m
3
3
3
Page 12
/day – g/sec –
3