8/10 GANG RECESSED STEEL CONCRETE FLOOR BOX FOR ROUND
COVERS - Installation Instructions
Catalog no.'s CFB10G55RE, CFB10G55RCRE
CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before installing or servicing.
NOTICE: For installation by a qualified electrician in accordance with national and local electrical codes, communication
standards, the following instructions, and any instruction included with individual devices.
NOTICE: Ensure data/communications circuits are separated from lighting/power circuits in accordance NEC and CE code
requirements.
Use with CFBS1R8CVRxx series round covers.
Use with CFBS1R8FFCVRxx series round furniture feed covers. CFBS1R8FF10GDIVKIT partition system required for
multi-service installations.
Use with CFBHUB2, 2 in. metallic conduit hubs, CFBHUB125PVC, 1-1/4 in. non-metallic hubs, or CFBHUB200PVC, 2 in.
non-metallic hubs may be used in place of knockout plates as needed.
Use with CFB8RCVRR075 stackable pre pour rings to increase concrete thickness over the box. Each ring adds 3/4" of concrete
over the box.
BEFORE CONCRETE POUR, SEE FIGURE 1
1.
Remove four #8-32 pan head screws [1] from top corners of floor box assembly and retain.
2.
Remove transition [2] and mounting plate [3] assemblies from box and retain.
3.
Make conduit connections in accordance with application and applicable electric codes. 2" trade size conduit hubs,
(CFBHUB2) or PVC conduit hubs (CFBHUB125PVC, CFBHUB200PVC) may be used in place of knockout plates [4] as needed.
4.
For same side feed-thru wiring, remove low voltage dividers [5] as necessary.
5.
Reinstall transition [2] on top of the mounting plate assembly [3]. Secure using #8-32 pan head screws [1] in corners.
6.
Cover visible openings and screws that penetrate the floor box with tape to prevent concrete from entering the box.
7.
Install leveling screws [6] as shown in Figure 1. Level box as required, positioning the floor box with the temporary cover [7]
even with slab level. Use leveling screws [6] and wire to keep the floor box from moving during concrete pour. See Table 1
for minimum depth of pour.
8.
Verify that flat head screws [8] holding the temporary cover [7] are secure. After tightening, cover screw heads and cover
edge with tape. Grease to aid in removal later.
9.
Pour concrete flush to the top of the temporary cover [7].
CFBHUB2
Conduit Hub
2 in. trade size
(sold separately)
Wiring Device - Kellems
Hubbell Incorporated (Delaware)
40 Waterview Dr.
Shelton, CT 06484
1-800-288-6000
www.hubbell-wiring.com
PD-3009
3/23
CFBHUB125PVC
PVC Conduit Hub
1-1/4 in. trade size
(sold separately)
CFB10G55RE
Page 1
ENGLISH
5-1/2"
6-1/4"

Publicité

loading

Sommaire des Matières pour Hubbell CFB10G55RE

  • Page 1 8/10 GANG RECESSED STEEL CONCRETE FLOOR BOX FOR ROUND COVERS - Installation Instructions ENGLISH Catalog no.'s CFB10G55RE, CFB10G55RCRE CAUTION: RISK OF ELECTRIC SHOCK. Disconnect power before installing or servicing. NOTICE: For installation by a qualified electrician in accordance with national and local electrical codes, communication standards, the following instructions, and any instruction included with individual devices.
  • Page 2 AFTER CONCRETE POUR, SEE FIGURES 2, 3, AND 4 Locate floor box, remove three screws [8] and remove temporary concrete cover [7]. CAUTION: Temporary concrete covers are intended to keep concrete residue from entering box during pour and are not intended to support loads. Replace with permanent flange/cover immediately after concrete has hardened.
  • Page 3 FRAN AIS Num ros de catalogue CFB10G55RE et CFB10G55RCRE ATTENTION - RISQUE DE CHOC LECTRIQUE. D brancher le circuit avant de proc der au montage ou la maintenance. AVIS - Doit tre install par un lectricien qualifi conform ment aux codes de l' lectricit nationaux et locaux, aux normes de communication, aux directives suivantes et toutes directives jointes aux dispositifs individuels.
  • Page 4 APR S LA COUL E DE B TON, CONSULTER LES FIGURES 2, 3 ET 4. Localiser la bo te de plancher, retirer les trois vis [8] et le couvercle temporaire pour b ton [7]. ATTENTION - Les couvercles pour b ton temporaires sont con us pour emp cher les r sidus de b ton de p n trer dans la bo te pendant la coul e et ne sont pas destin s supporter les charges.
  • Page 5 Wiring Device - Kellems HUBBELL M XICO garantiza este producto, de estar libre de defectos en materiales y mano de obra por un a o a partir de su compra. Hubbell reparar o reemplazar el art culo Hubbell Incorporated (Delaware) a su juicio en un plazo de 60 d as.
  • Page 6 DESPU S DEL VERTIDO DE CONCRETO, VER LAS FIGURAS 2, 3 Y 4 Ubique la caja de piso, retire los tres tornillos [8] y retire la cubierta de concreto temporal [7]. PRECAUCI N: Las cubiertas de concreto temporales est n dise adas para evitar que los residuos de concreto entren en la caja durante el vertido y no para soportar cargas.

Ce manuel est également adapté pour:

Cfb10g55rcre