Specifications

Application: fine filter HVAC, industrial
Frame: plastic, galvanised optional
Spacers: synthetic
Adhesion: N/A
Medium: synthetic
Packing: optional, polyurethane foam
Filter class according to EN779:2012: M6
Maximum final resistance: 450 Pa
Maximum temperature: 70°C
Maximum relative humidity: 90%

Installation

• Make sure the filter is installed correctly: intake side – clean air side
• Filter should be installed correctly: no leaks
• Packing should not be damaged
• Filter should be clamped down in four places
• Prevent the filter medium from doubling up
• Prevent the filter from being damaged during installation
• The system must operate for a few hours to obtain the result desired
• Filter installation registration: write down the date, type, initial resistance.