1.1 Important Instructions

IMPORTANT - SAFETY
!
Read this manual carefully and in its entirety before any
technical intervention on the device.
The operation must only be performed by qualified
personnel.
Installation and commissioning of product must be done
by following sequence describe below. Order of steps is
important and must be described.
Cut mains off before any intervention on device.
The power supply unit must be provided upstream with:
• a bipolar disconnecting device;
• a circuit breaker: 4 A - D Curve.
The device must be carried carefully and stored in proper
conditions (humidity and temperature).
The Installer must check that device has not been damaged
during transport and installation. A damaged product may
cause serious injury. A damaged product must never be
connected to the mains.
The device must never be connected to the mains if it
is not properly fixed to the wall with its housing properly
connected to protective earth (see first step of installation).
Replacing the original battery with a battery of incorrect
type may result in an explosion hazard. Used batteries must
be disposed of in compliance with recycling requirements.
This device is a class A device. In a residential environment,
this device can cause radio frequency interference. In this
case, the user may take appropriate measures.
Use 4 screws with a diameter up to 5 mm. Plugs
and screws must be adapted to type of wall. Each
fixing
plugs/screws
weight of 20 kg (80 kg split on each fixing screw).
Electrical shock risk symbol
Protective earth terminal
EATON Safety Power Supply (ZNO1031200 A)
must
support
a
minimum

Typical applications

The SPS is a two output-24V dc battery backed power
supply. It is a high efficiency switching power supply;
protected from overload and short circuits.
It is specifically recommended as an auxiliary power
supply unit for fire detection system components, such as
electromagnets, notification devices, etc.
Conformity to standards
15
DoP Nos:
SPS-24-1A5/BNS: SPS1A5CE
0333
SPS-24-2A5/BNS: SPS2A5CE
SPS-24-4A5/BNS: SPS4A5CE
This device complies with the following standards:
EN 54-4: 1997 / A1: 2003 / A2: 2005;
EN12101-10:2005 class A Env. class 1.

Recycling Instructions

Wasted electrical products should not be
disposed of with household waste. Please
recycle where facilities exist. Check with your
local authority or retailer for recycling advice.
September 2016 www.eaton.com

Instructions - English

3

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Sps-24v-2a5/bnsSps-24v-4a5/bnsSps-2423Sps-2433Sps-2453

Table des Matières