Télécharger Imprimer la page

Avanti SED67D0W Manuel D'instructions page 15

Publicité

Les langues disponibles

Les langues disponibles

Additionally, a 1/8" (0.3cm) N.P.T. (National Pipe Thread) plugged tapping,
accessible for test gauge connection, must be installed immediately
upstream of your dryer's gas supply connection.
Your dryer must be disconnected from the gas supply pipe system during
any pressure testing of the system.
This dryer must be connected to the gas supply piping with a listed
flexible gas connector that complies with the standard for connectors for
gas appliances, ANSI Z21.24 or CSA 6.10.
DO NOT reuse old flexible metal gas lines. Flexible gas lines must be
design certified by the American Gas Association (CGA in Canada).
Any pipe joint compound used must be resistant to the action of any
liquefied petroleum gas.
• As a courtesy, most local gas utilities will inspect a gas appliance
installation.
GAS IGNITION - Your dryer uses an automatic ignition system to ignite the
COMMONWEALTH OF MASSACHUSETTS INSTALLATION INSTRUCTIONS
Your dryer must be installed by a licensed plumber or gas fitter. A "T"
handle manual gas valve must be installed in the gas supply line to
installed dryer at location of operation. If a flexible gas connector is used
to connect dryer, the connector may not be longer than 3' (36", 91.5 cm).
WARNING
Gas leaks may occur in your system, creating a dangerous situation.
Gas leaks may not be detected by smell alone.
Gas suppliers recommend that you purchase and install a UL-
approved gas detector.
Install and use it in accordance with the manufacturer's instructions.
15
burner. There is no constant burning pilot.

Publicité

loading

Ce manuel est également adapté pour:

Sgd67d0wg