Rep.
Designation
FC0
Open limit switch
FCF
Close limit switch
D1/D2
Failure report Terminal strip (24V DC / 3A max)
TP/PE
D1
D2
+
16
-
15
-
14
+
13

The card resolution is 1°

10 KOhm input impedance if control with voltage (0-10V) / 100 Ohm input impedance if control with current (0-20mA or4-20mA)

The terminal temperature can reach 90°C

The used wires must be rigid (feedback voltages : 4 to 250V AC/DC)

For a use with a long wiring, the induction current generated by the wires mustn't be higher than 1mA

La tension de pilotage doit être de type T.B.T.S. (Très Basse Tension de Sécurité)

No common earth/ground connexion between the control (input and output signal) and the alimentation. (Type 0-20 or 4-20mA : 5V DC max.)
40
Rep.
Designation
FC1
Auxiliary limit switch 1
FC2
Auxiliary limit switch 2
Power supply
N
Ph
-
+
1
2
3
100V-240V 50/60Hz (100V-350V DC)
15V-30V 50/60Hz (12V-48V DC)
17
18
17
18
A
A
C
~
+
~
B
Motor
=
POSI MODELS
Feedback
4
5
6
7
8
SNAA690000
9