11.3 GENERIC HEAT DEMAND
A generic heat demand does not come from one of the three available heating circuits and/or from the DHW circuit. This type of
demand is called user demand and is used to provide heat to external units such as heating water in a swimming pool.
To enable this function, perform the following configuration procedure. Enter menu 2 from the Remote Control, as described in
section 5:
PROGRAMME
MENU
ROW
6030
CONFIGURATION
6046
1859
USER CR1
If the user demand is provided via a 0-10 V analogue signal, set parameter 6046 to "User demand CR1 10V". Also set signal
characteristics using the following parameters:
Valore tens. 1 H2
6049
modulo 1
11.4 OTHER CONFIGURATIONS
Further configurations are summarised below:
QX21 relay
Alarm output K10
System pump Q14
Time setting 5 K13
Refrigeration request K28
Water refill K34
Fan shutdown K38
BX21 sensor
Buffer sensor B4
Buffer sensor B41
Buffer sensor B42
H2 input
Error/alarm message
Boiler flow switch
Boiler temp limiter
Consumer request VK1 10V
Pressure measurement 10V
Preselected output 10V
* To use the functions set the characteristics of the analogue signal using the following parameters present in the Configuration menu of the
Remote Control:
Voltage value 1
6049
6050
H2 module 1
7104900.03 (1-11/13)
VALUE TO SET
Cons circuit pump VK1 Q15
Consumer request VK1
factory setting = 70°C
6050
Valore 1 H2 modulo 1
Alarm (e.g.: condominium)
Pump active at every heating or external demand
Contact commanded from "aux hourly programme"
Cooling demand from chiller circuit 1
Boiler automatic filling valve
External fan control
Storage boiler sensor for heating (higher)
Storage boiler for heating (lower)
Third storage boiler probe for heating (half of storage boiler)
External alarm signal
Boiler flow switch command (only to use if not on the boiler)
Boiler thermostat command (only to use if not on the boiler)
External demand 1 with 0-10V signal (*)
Pressure measurement with 0-10V signal (*)
Boiler power adjustment according to 0-10V signal (*)
Funct value 1 H2
6051
module 1
External demand 1 pump enable ( relay QX21 output)
External demand 1 contact
Heating flow temperature for external demand 1
Valore tens. 2 H2
6051
modulo 1
Voltage value 2 H2
6052
module 1
34
DESCRIPTION
6052
Valore 2 H2 modulo 1
Funct value 2 H2
module 1