To reposition the air thermistor on the outdoor unit....15 Daikin website (publicly accessible). 7 Finishing the outdoor unit installation ▪ The full set of latest technical data is available on the Daikin To close the outdoor unit............16 Business Portal (authentication required).
4 12]. ▪ This manual. See "6 Electrical comply with instructions from Daikin and with applicable ▪ The wiring diagram, which is delivered with the unit, legislation and are executed ONLY by authorised persons. located at the inside of the service cover. For a Mounting the outdoor unit (see "4.2 Mounting the outdoor...
Discharge grille (upper + lower part) Installation manual – Discharge grille NOTICE Unpacking. When you remove the top packaging/ accessories, hold the box containing the discharge grille to prevent it from falling. EPRA08~12EAV3+W1 Installation manual Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
WARNING Make sure installation, servicing, maintenance and repair comply with instructions from Daikin and with applicable legislation and are executed ONLY by authorised persons. (mm) Make sure not to cover the drain hole in the bottom plate of the unit.
O-ring. Make sure the O-ring is installed correctly to prevent leakage. To open the outdoor unit DANGER: RISK OF ELECTROCUTION DANGER: RISK OF BURNING/SCALDING 4.2.3 To provide drainage Make sure that condensation water can be evacuated properly. EPRA08~12EAV3+W1 Installation manual Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
2 Connect the field piping to the shut-off valve. To attach the compressor cover 3 Connect the field piping to the outdoor unit water outlet. piece Required accessory (delivered with the unit): Installation manual EPRA08~12EAV3+W1 Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
▪ Install freeze protection valves (field supply) at all lowest points of the field piping. EPRA08~12EAV3+W1 Installation manual Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
ALWAYS use multicore cable for power supply cables. CAUTION Do NOT push or place redundant cable length in the unit. NOTICE The distance between the high voltage and low voltage cables should be at least 50 mm. Installation manual EPRA08~12EAV3+W1 Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
▪ Connect the wires to the terminal block and the earth screw. ▪ Fix the cable with cable ties. Wires: (2+GND)×0.75 mm². Wiring must be double insulated. L N PE Maximum power allowed for drain tube heater = 115 W (0.5 A) — EPRA08~12EAV3+W1 Installation manual Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
V3 models. For more information about the power saving function ([9.F] or overview field setting [E‑08]), see the installer reference guide. 6.4.2 In case of W1 models 1 Power supply cable: Installation manual EPRA08~12EAV3+W1 Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
▪ Fix the cable with cable ties. Required accessory (delivered with the unit): Wires: (2+GND)×0.75 mm². Wiring must be double insulated. Thermistor fixture. Maximum power allowed for drain tube heater = 115 W (0.5 A) — Click EPRA08~12EAV3+W1 Installation manual Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
"7.3 To remove the discharge grille, and put the grille in position" [ 4 17] safety 4 Align the ball stud and hook on the grille with their counterparts on the unit. EPRA08~12EAV3+W1 Installation manual Daikin Altherma 3 H MT 4P634882-1B – 2021.09...
9 Technical data Technical data A subset of the latest technical data is available on the regional Daikin website (publicly accessible). The full set of latest technical data is available on the Daikin Business Portal (authentication required). Piping diagram: Outdoor unit...