Modbus address
[OFF/1...247]
[OFF=not in use
1=external NTC sensor
2=DI2 door/window switch
3=DI2 condensation switch]
Set point area
centre
[18...26 °C]
PWM pulse width
[20...1200 s]
Fan stage
simultaneously with
the valve stage [on/off]
Sequence of
heating stages
[Valve/VAV]
Minimum of
cooling actuator
[0...50 %]
Fan output
scaling, high end
[0...100 %]
Fan speed 3
voltage
[0...10.00 V]
6-way valve cooling,
high limit [0...10.00 V]
Le diagramme continue sur la page suivante.
Produal Oy | Keltakalliontie 18, FI 48770 Kotka, FINLANDE | Tél : +358 10 219 9100 | info@produal.fr
Publié : 15.07.2021
Parity bit
Modbus speed
[9.6/19.2/38.4/56]
[none/Even/Odd]
DI2 operation
Temperature
direction
sensor adj.
[0=nc
[-3...+3 °C]
1=no]
Set point area
Control mode
limits ± [0...16 °C]
[P/PI]
Integration time
Cooling output mode
[50...50000 s]
[DIR=direct
REV=reversed]
Fresh air control
Night operation mode
Night mode dead
[0=CO
/T, 1=DAY/
[DZ=dead zone
zone
2
T, 2=CO
, 3=DAY,
FG=frost guard]
[0.0...10.0 °C]
2
4=DAY/CO
/TE]
2
Maximum of
Minimum of
cooling actuator
heating actuator
[50...100 %]
[0...50 %]
Fan output
Fan type
scaling, low end
[3coil=3-speed fan
[0...100 %]
EC=EC motor]
Fan output boost
These values must be OFF,
duration
because these functions are not in
[0...10 s]
use in this version of the controller
Ces informations peuvent être modifiées sans notification préalable.
DI1 usage
DI1 operation
DI1 delay passive
[OFF=not in use
direction
to active
1=control to day mode
[0=nc
[0...60 min]
with nc/no switch]
1=no]
Thermostat
Thermostat
Dead zone
function, cooling
function, heating
[0.0...3.0 °C]
[off/on]
[off/on]
Heating output mode
Cooling stages
Sequence of
[DIR=direct
[1St=1 pcs
cooling stages
REV=reversed]
2St=2 pcs]
[Valve/VAV]
Frost guard
Set point after night to
thermostat set point
day mode change
[8.0...50.0 °C]
[off=last user setting
on=set by Modbus]
Maximum of
Minimum of fan
Maximum of fan
heating actuator
output
output
[50...100 %]
[0...50 %]
[50...100 %]
Fan usage
Fan speed 3
Fan speed after night to
[OFF=not in use,
disabled
day mode change
1=cooling, 2=heating,
[OFF=not disabled
[off=last user setting
3=cooling and heating]
on=set by Modbus]
6-way valve output
6-way valve
[OFF=not in use,
heating, low limit
COOL=Y3, HEAT=Y4]
[0...10.00 V]
DI1 delay active
Minimum VAV output
to passive
in day mode
[0...60 min]
[0...100 %]
Set point position
Proportional band
in the dead zone
[1...32 °C]
[0...100 %]
VAV for heating
Heating stages
[on/off]
[1St=1 pcs
2St=2 pcs]
Duration of
Automatic reset of
temporary day mode
the setpoint and fan
[0...480 min]
speed after op. mode
change [off/on]
Minimum of VAV
Maximum of VAV
output
output
[0...50 %]
[50...100 %]
Fan speed 1
Fan speed 2
voltage
voltage
[0...10.00 V]
[0...10.00 V]
6-way valve
6-way valve
heating, high limit
cooling, low limit
[0...10.00 V]
[0...10.00 V]
FR - 1150400ug
8 (42)