4.4.
Gas connection
Connection to the gas line is made on the right-hand side.
Check that the type of gas and the gas pressure correspond with the specifications
on the specification plate.
An approved gas cock must be installed in the gas line as close as possible to the
unit in a place that is always accessible.
No strain must be remaining when the connection is made.
Check that there are no gas leaks in the line (using e.g. a soap and water solution).
For lines up to +/- 10 m, 3/8" G pipe or copper pipe of 10/12 diameter is sufficient.
For more than 10 m, use ½" or copper pipe of 13/15 diameter.
4.5.
Electrical connection
The gas heater has been equipped with an electrical (heat resistant) cable of
approx. 1 m, which should be connected to the earthed mains (230 V). This can be
done through using a plug or a permanent connection. Power can afterwards be
removed by disconnecting the plug connection that has been built into the appli-
ance.
1
2
1
0
3
2530GA(P)
1 B
1
1 A
1 fan
2 AMP plug
3 switch
4 test push button
5 thermostat
- 34 -
1
2
3
4
2
5
03.27603.000