A switch on the control panel is labeled "Set Exercise"
(depicted on page 10).The specific day and the specific time
of day this switch is pressed is programmed into the
control board memory.This date and time is then used to
automatically initiate the system exercise cycle.
To perform the Set Exercise procedure:
1.
Choose the day and time you want your Home
Generator System to exercise.
2.
On that day and time, set the AUTO/OFF/MANUAL
switch to OFF.
3.
Press and hold down the "Set Exercise" switch.The
Diagnostic LED blinks.
4.
Hold the switch down until the Diagnostic LED stops
blinking. Release the Set Exercise switch.
5.
Set the AUTO/OFF/MANUAL switch to AUTO. "Set
Exercise" is complete.
For example, if you press the "Set Exercise" switch on
Sunday morning at 10:00 AM, the unit will run an exercise
cycle the following Sunday at 10:00 AM.
NOTE: "Set Exercise" will only work if the unit is in the
Automatic mode and this exact procedure is followed.The
exerciser does not need to be re-set if the 15 Amp fuse is
removed or changed.The exerciser will need to be re-set if
the 12 Volt DC battery is disconnected.
If you want to change the day and time the unit exercises,
simply perform the "Set Exercise" procedure at the exact
weekday and time you want it to take place.
Briggs & Stratton Power Products Home Generator System
Owners Manual
www.mymowerparts.com

SPECIFICATIONS

Generator

Model . . . . . . . . . . . . . . . . . . . . 01679-0
Rated Maximum Power (LP*). . . 10.0 kW
Rated Maximum Load Current:
at 240 Volts . . . . . . . . . . . . . . . 41.7 Amps
at 120 Volts . . . . . . . . . . . . . . . 83.3 Amps
Rated AC Voltage . . . . . . . . . . . . 120/240 Volts
Rated Frequency . . . . . . . . . . . . 60 Hz at 3600 rpm
Phase . . . . . . . . . . . . . . . . . . . . . Single Phase
Power Factor . . . . . . . . . . . . . . . 1.0
NG Fuel Supply Pressure. . . . . 5-14 in W.C. (127-356 mm)
LP Fuel Supply Pressure. . . . . . 11-14 in W.C. (279-
Normal Operating Range . . . . -20°F (-28.8°C) to 104°F
Output Sound Level . . . . . . . . 70 dB(A) at 23 ft. (7 m) at
Shipping Weight . . . . . . . . . . . . 482 lbs.
* Natural gas rating will depend on specific fuel but typical
derates are between 10 to 20% off the LP gas rating.

Transfer Switch

Maximum Circuits . . . . . . . . . . . 10
Maximum Load/Circuit:
from Generator . . . . . . . . . . . 41.7 Amps
from Load Center. . . . . . . . . . 50 Amps
Maximum Watts . . . . . . . . . . . . . 10,000