10
WALL CONTROLS
(CONT'D)
AUXILIARY CONTROL –These controls can be paired with central controls or combined together.
(+ → + ; - → -)
*Maintain polarity between control and HRV
T SERIES
FEATURES
T4*
• 20- minute timer with LED light
• Boosts system to high speed with the touch of a button
• Up to 5 can be used in one system
• Use in bathroom, kitchen, laundry room
T5*
• 20/40/60 minute timer with LED light
• Boosts system to high speed with the touch of a button
• Up to 5 can be used in one system
• Use in bathroom, kitchen, laundry room
RD-1
• Rotary dial Dehumidistat
• Multiple units can be used
• We recommend setting the relative humidity above 80% during the summer
BALANCING
Balancing must be completed using the Greentek ECO-Touch ® Programmable Touch Screen Wall Control
CONNECTS TO
+T
-T
ENTERING BALANCING
MODE
In the options menu during
the initial 5 second countdown
sequence, long press on "ECO"
D
area for 5 seconds to enter
D
basic balancing mode.
The supply and exhaust fans are
adjusted on high speed only and
the offsets are proportionally
applied to the medium and low
speed automatically.
AUTO
OPTIONS
AUTO
OPTIONS
High
Low
STAGE 1
(ADJUST LEVEL OF EXHAUST FAN IN HIGH SPEED):
• In this step, balance exhaust fan and measure airflow on the
exhaust air side
• Pressing on "up" or "down" will adjust the fan speed in increments
of 1%.
• Once the desired exhaust airflow is reached, press on "next" and
move on to the next stage.
MANUAL
STAGE 2
(BALANCE SUPPLY FAN ONLY IN HIGH SPEED):
• In this step, balance supply fan and measure airflow on the supply
air side
• Pressing on "up" or "down" will adjust the fan speed in increments
of 1%.
• Once happy with the outcome, press on "next" to complete
balancing
MANUAL
• The supply and exhaust offset values will be proportionally applied
to low and medium speed as well.
NEXT
11
Supply
manometer
High
Low
Exhaust
manometer
AUTO
MANUAL
OPTIONS
0 %
ADJUST
NEXT
AUTO
MANUAL
OPTIONS
0 %
BALANCE
NEXT