Specifications and Accuracy
Polarity: Automatic
Voltage Range: 19 to 1000 VAC, 5 to 1000 VDC
Internal Basic Load: 0.8 W at 600 V (approximate)
Input Impedance: 460 kΩ || 160 pF (nominal)
Number of LEDs: 14
LED Threshold: The following table gives nominal thresholds.
AC Tolerance: ± (2.5% of reading + 4 V)
DC Tolerance: ± (1% of reading + 2 V)
AC Marking
24
48
120
208
240
277
347
480
600
1000
Frequency Range: DC and 45 to 65 Hz
Test Current: Less than 2.5 mA
Wireless Electric Field Detection (EF):
Indication: Bar graph segments and audible beep tones are proportional
to the field strength.
Detection Frequency: 50/60 Hz
Detection Antenna: Top of unit
Typical Voltage
15 V to 55 V
30 V to 95 V
55 V to 170 V
above 120 V
12
AC Threshold
19
38
96
166
224
259
312
414
540
800
GT-95 Bar Graph Indication
DC Marking
6
12
24
36
48
60
72
110
220
380
– –
– – –
– – – –
DC Threshold
5
10
19
30
42
54
66
91
176
304