Télécharger Imprimer la page

Publicité

Configuring the xtender
rcc 02/03
battery monitor
Ubat
12.09 Vdc
2.10 Adc
Soc
46.1 %
2h59
soc history
100%
-4
-3
-2
-1
day
Displaying
real time user
information
12
bsp setting
con guration assistant
Configurating parameters
Basic settings
⋅ Voltage of the system
⋅ Nominal capacity
⋅ Nominal discharge time (C-rating)
⋅ Nominal shunt current (500A or 1200A)
⋅ Nominal shunt voltage
⋅ Reset of battery history
⋅ Restore default/factory settings
Advanced settings

Technical data

bsp
Supply voltage range
Supply current
Input voltage range
Shunt measurement input range
RMS continuous current @ 25°C
Maximum measurable peak current
Voltage measurement accuracy
Current measurement accuracy
Battery capacity
Operating temperature range
IP 20
7 ... 85Vdc
9 mA @ 12V
5 mA @ 24V
3 mA @ 48V
7 ... 85Vdc
± 195 mV
± 500 A (bsp 500)
± 1200 A (bsp 1200)
± 1950 A (bsp 500)
± 4680 A (bsp 1200)
0.3%
0.5%
20 ... 20000 Ah
-20 ... 55°C
13

Publicité

loading