The CTE can accept line input power from an external, UL294, UL603
or ULCS318/ULCS319 listed power supply capable of sourcing at
least 500 mA@12 or 24 VDC must be provided.
POE and POE+ power can also be used to power by the CTE.
Power output from the CTE is determined by the choice of power
input. See the table below.
The CTE power output to the credential reader is always limited
L
to 0.3A. When 24 volts line power input is provide the CTE can
power a QEL directly from the LOCK powered output.
To be used with a UL Listed UL294, UL294B, UL603, or UL60950
POE/POE+ power source. Note: For CUL installations the POE/POE+
source and power supply is required to be ULC-S318 or ULC-S319
listed.
RS485 & Wiegand¹
Input Power Source
Voltage
POE (44-57V 15.4W)
12 VDC
POE+ (50-57V 25.5W)
12 VDC
LINE 12VDC (2A)
12 VDC
LINE 12VDC (4A)
12 VDC
LINE 24VDC (2A)
12 VDC
LINE 24VDC (4A)
12 VDC
DRY Contact Relays, LOCK, ALARM, and AUX are all rated to
handle up to 30V 2A individually.
¹ WIEGAND reader not supported at this time
* CTE will trigger a fault condition and turn off POWERED output if
maximum current value in table is exceeded.
Power
WARNING
HIGH VOLTAGE
Symbol indicates risk of
electric shock!
Do not remove!
Reader Power
Powered Outputs
Lock, Alarm, and
Aux Relays
Current
Voltage
(shared)
10.2 -
300mA
10.2 -
(MAX)
12 VDC
10.2 -
300mA
10.2 -
(MAX)
12 VDC
10.2 -
300mA
10.2 -
(MAX)
12 VDC
10.2 -
300mA
10.2 -
(MAX)
12 VDC
10.2 -
300mA
22 - 24
(MAX)
VDC
10.2 -
300mA
22 - 24
(MAX)
VDC
The CTE has internal tamper detection which is recorded in the CTE
audit report. CTE inputs require relay contact closure or switched open/
closed contact closure.
Input Description Table
INPUTS
REN
REN GND
REX
REX GND
DPS
DPS GND
Current
(shared)
REL
500mA
(MAX)*
REL GND
1.5A
(MAX)*
TAMP
1.5A
TAMP GND
2.0A
(MAX)*
CTE has input switch settings that allow the input active or inactive
to be changed. the switches are directly above the INPUT LEDs and
1.5A
INPUT connector blocks.
2.0A
(MAX)*
Switch Settings Table
REN (Request to Enter)
REX (Request to Exit)
DPS (Door Position Switch)
REL (Remote Release)
TAMP (Reader Tamper)
Inputs
When the switch activates, CTE
will activate the AUX RELAY.
Request to enter
LOCK RELAY must already be
activated and UNLOCKED
Electrical ground (common) for
Ground
the CTE
When the switch activates, the
Request to exit
CTE will activate the LOCK
RELAY
Electrical ground (common) for
Ground
the CTE
When a DPS is installed, the
CTE will trigger an alert, forced
Door position
door, propped door, and can
switch
also activate the ALARM RELAY
if configured in this manner with
the ENGAGE mobile application
Electrical ground (common) for
Ground
the CTE
When the switch activates, the
CTE will activate the LOCK
Remote Release
RELAY as a remote release or
buzz in action
Electrical ground (common) for
Ground
the CTE
When the switch activates, the
Reader Tamper
CTE will trigger an alert
Electrical ground (common) for
Ground
Wiegand applications.
Set the DIP switch for each input to
NO (normally open) or NC (normally
closed) such that the LED illuminates
when the input is active.
Description
5