READ ALL INSTRUCTIONS BEFORE INSTALLING FAST CABLE LINK
FCL Size * Rated Load Wire Rope Dia. Wire Rope Type
FCL 1
23 lb / 10kg
FCL 2
100 lb / 45kg
FCL 3
200 lb / 90kg
FCL 4
600 lb / 272kg
FCL 5
1,000 lb / 453kg
WARNING
DO NOT EXCEED THE RATED LOAD OF THE FCL
FAST CABLE LINK
*Note:
The Rated Load is the applied load in a true vertical orientation.
FCL System Recommendations:
• Do not exceed the safe working load (see Maximum SWL for Various
Angles).
• FCL Series load ratings are applicable only when used with wire ropes
from Thomas & Betts.
• Do not use for overhead lifting or hoisting.
• Do not paint cable near working area of FCL device.
• Do not apply lubricant to the FCL system.
• Keep product clean and free of dirt.
• Do not use in chlorinated or caustic atmospheres.
• For use in dry locations only.
• Do not use in excess of 200°F.
BEFORE INSTALLATION:
 Use only Wire Rope by Thomas & Betts.
 Use only the Wire Rope size as speci ed on the FCL Fast Cable Link
being used.
 Visually inspect the wire rope for broken or deformed strands.
DO NOT use the cable if there is any evidence of broken or deformed
strands (i.e. at spots, kinks, sharp creases, fraying, etc.)
 Make certain the wire rope is clean. Remove any debris, grease or oil.
 Visually inspect the FCL Fast Cable Link through both insertion ports to
assure no foreign material is located in the wire rope paths.
 Visually inspect exterior surfaces. DO NOT use if there is any evidence of
dents, cracks, damage to riveted connection, or if body halves are loose.
 Inspect both Locking Roller Slots (see FIGURE A). Make certain the
Locking Roller Spring is in contact with the Locking Roller. DO NOT use
FCL if the Spring(s) is missing or is not contacting the Locking Roller.
IMPORTANT SAFETY NOTE:
Before use, insert correct size wire rope through both Cable Entry Ports
so that it comes through the Cable Exit Ports. Push the Release Pin and
remove Wire Rope. DO NOT use if the Locking Roller Spring does not
return to its original postion (in contact with the Locking Rollers) as
shown in FIGURE A.
TA04636 D
Page 1 of 4
FAST CABLE LINK
Installation Instructions
3/64"
Galvanized Steel
5/64"
Galvanized Steel
1/8"
Galvanized Steel
3/16"
Galvanized Steel
1/4"
Galvanized Steel
FCL Series Fast
Cable Link
WARNING
DO NOT USE FOR OVERHEAD
LIFTING OR HOISTING
Locking
Roller
Slot
FIGURE A
Cable Insertion
Wire Rope Direction
(Fig. B.1)
Cable
Exit
6" MIN.
Port
Locking
Roller
Arrow
Indicator
Cable Insertion
Cable
(Fig.B.1)
Entry
Port
FIGURE B
ENGLISH
Locking
Roller
Spring
Locking
Roller
Cable
Entry
Port
Figure B.1
Arrow
Indicator
Diameter of
Wire Rope as
indicated
Cable
Exit Port
Suspended device
or structure

Publicité

loading

Sommaire des Matières pour Thomas & Betts Kindorf FCL Fast Serie

  • Page 1 ENGLISH FAST CABLE LINK Installation Instructions IMPORTANT: READ ALL INSTRUCTIONS BEFORE INSTALLING FAST CABLE LINK FCL Size * Rated Load Wire Rope Dia. Wire Rope Type FCL Series Fast FCL 1 23 lb / 10kg 3/64” Galvanized Steel FCL 2 100 lb / 45kg 5/64”...
  • Page 2 ENGLISH WARNING NOT RATED FOR SEISMIC LOAD APPLICATIONS INSTALLATION: Insertion of Wire Rope through FCL (FIGURE B): NOTE: MAKE CERTAIN APPLIED LOAD IS FULLY SUPPORTED INDEPENDENTLY OF THE FCL CABLE LINK UNTIL INSTALLATION IS COMPLETE. Step 1 Insert correct diameter Wire Rope through rst Cable Entry Port.
  • Page 3: After Installation

    ENGLISH WARNING NOT RATED FOR SEISMIC LOAD APPLICATIONS AFTER INSTALLATION: • Check and make certain that a minimum of 6” of wire rope is present beyond the exit port of the FCL (see FIGURES B and C). • Make certain the load does not exceed the rated load of the FCL in accordance with the load chart, Maximum SWL for Various Angles.
  • Page 4 FCL 1 FCL 2 FCL 3 FCL 4 FCL 5 Note: TA04636 D Page 4 of 4...
  • Page 5 Français MAILLON RAPIDE POUR CÂBLES Instructions d'installation IMPORTANT : LIRE TOUTES LES INSTRUCTIONS AVANT D'INSTALLER UN MAILLON RAPIDE POUR CÂBLES Raccord rapide pour Taille * Charge Diamètre du Type de câble câble série FCL du FCL nominale câble métallique. métallique FCL 1 23 lb / 10kg 3/64”...
  • Page 6 Français AVERTISSEMENT N'EST PAS CLASSÉ POUR DES APPLICATIONS DE CHARGE SISMIQUE INSTALLATION : Insertion du câble métallique dans le FCL (FIGURE B): REMARQUE : VEILLER À CE QUE LA CHARGE APPLI- QUÉE SOIT TOTALEMENT SUPPORTÉE INDÉPENDAM- MENT DU MAILLON DE CÂBLE FCL JUSQU’À CE QUE L'INSTALLATION SOIT TERMINÉE.
  • Page 7: Après L'installation

    Français AVERTISSEMENT N'EST PAS CLASSÉ POUR DES APPLICATIONS DE CHARGE SISMIQUE APRÈS L'INSTALLATION: • Vérifier qu'il y a au moins 6 po de câble au-delà de l'orifice de sortie du FCL (voir FIGURES B et C). • Veiller à ce que la charge ne dépasse pas la charge nominale du FCL, conformément au tableau de charge, Charges maximales d'utilisation pour différents angles.
  • Page 8 FCL 1 FCL 2 FCL 3 FCL 4 FCL 5 Remarque: TA04636 D Page 4 de 4...

Ce manuel est également adapté pour:

Kindorf fcl 1Kindorf fcl 2Kindorf fcl 3Kindorf fcl 4Kindorf fcl 5