5. APPENDIX
5. App end ix
5.1 Paramètre et la liste des données AF
Analog inputs
Room_Temperature
Supply_Air_Temp
Room_Humidity
Pressure_SupplyFan
Analog outputs
Supply_Fan_Speed
Heating_Signal
Digital inputs
Fan_Alarm
HeatingCoil_Alarm
HpLp_Alarm
Comp_Overload
Filter_Dirty
Fire_Alarm
WCC_Heat_Demand
FunctionSwitch
Digital outputs
Supply_Fan_Start
External_Fan_Start
Compressor_A
Compressor_B
Heating_Coil_Pump
Common_Fault
WCC_Pump
Damper_Return
Damper_Outdoor
Pseudo analog
Return_Air_Calc
Supply_Air_Calc
Heat_Demand
Supply_Airvolume
Humidity_Room
Temperature_Room
Min_Supply_Temp
Max_Supply_Temp
Supply_Fan_High
Supply_Fan_Low
Pseudo digital
Wake_up_Humid
Wake_up_Temp
Program_Status
Unit_Status
Function
Return air sensor
Supply air duct sensor
Humidity duct/room sensor
Pressure over supply fan
Signal supply fan
Actuator heating coil
Thermo relay / flow switch
Frost thermostat
HP / LP pressostat switch
Thermo relay compressor
Filter switch
Fire thermostat
External heat signal
Function switch
Supply air fan start
External fan start
Compressor A
Compressor B
Pump heat coil
Common fault
Pump water condenser
Return air damper
Outdoor damper
Calculated temperature
Calculated temperature
Calculated demand
Supply air volume
Set point
Set point
Set point
Set point
Set point
Set point
Set point
Set point
Status time program
Status time program
Comment
Temperature in pool hall
(sensor placed before heat exchanger inside unit)
Supply air temperature (sensor placed after heating coil)
Humidity level in pool hall
(sensor placed either in return air duct or in pool hall)
Pressure transmitter supply fan
(sensor placed in fan section)
Supply fan signal for inverter
Degree of heating coil valve opening
(100% means fully open valve)
Thermo relay fan motor / frequency inverter and flow switch
(Normal/Alarm)
Frost thermostat for LPHW coil (Normal/Alarm)
HP/LP switch for compressor (Normal/Alarm)
Thermo relay for compressor (Normal/Alarm)
Filter switch for fresh / return air filter (Normal/Alarm)
Temperature sensor in supply air duct and return air inside unit
(Normal/Alarm)
External heat signal to start up the water cooled condenser
Setting function switch in panel front
Signal for supply air fan start (ON/Off)
Signal for external fan start (On/Off)
Signal for compressor A start (On/Off)
Signal for compressor B start (On/Off)
Signal for water pump heating coil (On/Off)
Signal for common fault relay (On/Off)
Signal for pump water cooled condenser (On/Off)
Return air damper open / closed.
Outdoor damper open / closed.
Calculated temperature for return air
Calculated temperature for supply air
Calculated demand for heating (55-100%) or cooling (45-0%)
Actual supply air volume
Set point for humidity
Set point for temperature
Set point for minimum supply air temperature
Set point for maximum supply air temperature
Set point for minimum supply air volume
Set point for maximum supply air volume
Set point for wake up function humidity (On/Off)
Set point for wake up function temperature (On/Off)
Shows if the unit is running in open or closed mode plus fan
speed
Shows if pool is open or closed
22