Fendall 2000
1. Inspect label and review Expiration Date to determine if cartidge is current and ready for use. (See Fendall 2000
Installation and Operation Manual Section C for detailed instructions.)
2. Install Sterile Cartridge by holding the side handles, making sure the nozzle and tube are facing downward and the
front label is facing out.
CAUTION: CARTRIDGE WEIGHS APPROX. 60 LBS (27 KG). Two people lifting cartridge is strongly recommended for
installation.
3. Release the four straps by cutting the zip-ties. Ensure that the nozzle and tubing is fully extended from the cartridge.
Fig. 1
4. Hang cartridge on brackets and push cartridge all the way back. Fig. 2
5. Remove the blue poly-bag protecting the nozzle (let the nozzle hang in the basin below).
6. Compress the waste reservoir by pushing it upward. Slide all four straps (two front & two rear) into the hooks,
making sure the straps are not twisted. Visually inspect all four corners of the Bottom Plate, making sure they are
equal in height.
WARNING: If waste reservoir is not properly compressed or if the straps are not installed into the hooks, the unit will
not function properly on activation. Make sure the area underneath the Eyewash Station is kept clear.
7. Make sure the drain spout is closed. Fig. 3
8. Place the front panel back on the unit and close side panels.
9. In event of alarm activating before station is armed, see ALARM SHUT-OFF PROCEDURE (Below).
10. Open the door and pull the head rest towards you.
11. Pull out the nozzle from the basin. Slide the nozzle into the nozzle compartment, making sure the tube is not twisted
and that the small locking hub of the wire tie is facing towards the inside of the unit. Fig. 4
12. Push the headrest back to its original position until an audible 'click' is heard. Close the door by pressing the center
of the door and a 'click' will be heard confirming the nozzle is engaged.
13. Unit is now armed and ready for use.
14. In 3 days come back to the unit to check for leaks or salt residue by the nozzle and at the base of the unit to ensure
proper installment.
Alarm Shut-off Procedure
1. Locate small blue button inside door of station.
2. Press and hold button for approximately 3-5 seconds or until alarm shuts-off.
3. If still setting up station, complete Section C.
4. To rearm alarm, close station door. ALARM IS NOW ARMED.
Black Zip-tie
Fig. 1
Sperian Eye & Face Protection, Inc. • 825 East Highway 151 • Platteville, WI 53818 USA • 1-800-336-3255
Cartridge Quick Installation
Fig. 2
Part # 32-005631 Rev. C
Fig. 3
Fig. 4

Publicité

loading

Sommaire des Matières pour Sperian Fendall 2000

  • Page 1 Cartridge Quick Installation ™ 1. Inspect label and review Expiration Date to determine if cartidge is current and ready for use. (See Fendall 2000 Installation and Operation Manual Section C for detailed instructions.) 2. Install Sterile Cartridge by holding the side handles, making sure the nozzle and tube are facing downward and the front label is facing out.
  • Page 2 Cartucho Fendall 2000 - Instalación Rápida ™ 1. Inspeccione la etiqueta y observe la fecha de vencimiento para determinar si el cartucho aún está utilizable y listo para usarse. (Las instrucciones detalladas aparecen en la sección C del Manual de Instalación y Utilización – Fendall 2000.)
  • Page 3 1. Lisez la date d’expiration de l’étiquette pour vérifier que la cartouche peut être utilisée. (voir la section C du Manuel d’installation et d’utilisation Fendall 2000 pour plus de détails) 2. Installez la cartouche stérile en tenant les poignées latérales et en vous assurant que le gicleur et le tube sont tournés vers le bas et l’étiquette vers l’extérieur.